ECR International CACG Installation, Operation And Maintenance Manual Download Page 38

CACG/CAHG/CAHJ & CACH/CAHH/CAHK 

Air Handlers

•  Installation, Operation and Maintenance Manual  •

Comfort where it counts 

38

 

P/N 240008108, Rev. G [07/08/10]

CACH/CAHH/CAHK Microprocessor Controller Operation

NOTICE

When power is fi rst applied to the con-
trol or aft er a power outage there is a 
three minute delay before the compres-
sor or electric heat will energize. Th

 is is 

to protect the unit from short cycling due 
to loss of power.

NOTICE

Th

  e controller must be confi gured with 

Remote Thermostat NO

 to operate us-

ing the infrared remote controller. See 
(Table 6, pg. 32) for details. (Remote 
Th

  ermostat YES means the unit will be 

controlled by a wall thermostat.)

Handheld remote operation

When power is fi rst applied to the control or 
aft er a power outage there is a three minute 
delay before the compressor or electric heat 
will energize. Th

  is is to protect the unit from 

short cycling. 

Pointing the remote

When entering commands into the remote,  
make sure it is pointed toward the cassett e’s 
infrared receiver window (see  Figure 34, 
Page 33 ). Th

 e cassett e will respond with a 

beep indicating that it has successfully re-
ceived the transmitt ed information.

Synchronization

There may be occasions when the remote 
and the cassett e’s main control board mode 
synchronization or are not in the same mode.  
Th

  is can happen if commands are entered 

into the remote, but it is not pointed at the 
cassett e.

To re-synchronize:

Enter any command into the remote 

• 

while pointing it at the cassett e’s infrared 
receiver window.

Alternatively, hold the POWER/SEND 

• 

butt on for two seconds. All of the optional 
remote’s sett ings will be transmitt ed to the 
cassett e. Th

 e cassett e will respond with a 

beep, indicating that it has successfully 
received the transmitt ed information.

Temperature indication

Th

  e room temperature displayed on the re-

mote is the temperature at the remote.  Th

 e 

microprocessor control located in the cassett e 
does not read the remote’s temperature — it 
uses a sensor located in the return air of the 
cassett e. 

Therefore, the warming or cooling of the 
remote alone will not eff ect the operation of 
the Cassett e.  Th

 e Cassett e will react to its local 

temperature sensing element and the setpoint 
selected and transmitt ed by the remote.

Transmission limits

Th

  e remote has a useful transmission distance 

approximately twenty (20) feet when perpen-
dicular to the face of the Cassett e.  However, 
this distance will vary and decrease when the 
angle of transmission is not perpendicular. 
Th

  is distance may also vary depending on the 

lighting in the room. 

Hibernate mode

If there is no activity on the remote for ten 
minutes, it will enter a hibernate mode and the 
display will go dark. While in hibernate mode, 
pressing any butt on will awaken the remote.  
Th

  e remote will return to the mode it was in 

prior to entering hibernate mode.

Summary of Contents for CACG

Page 1: ... CAHJ12 CAHK12 CAHG24 CAHH24 Units 9 000 12 000 18 000 24 000 Btuh 2 6 3 5 5 3 7 0 kW Straight cooling only CACG36 CACH36 Units 30 000 36 000 Btuh 8 8 10 5 kW Installation Operation and Maintenance Manual ECR International Inc 2201 Dwyer Ave Utica NY 13501 www enviromaster com An ISO 9001 2008 Certified Company P N 240008108 Rev G 07 08 10 CAHK12 ...

Page 2: ...CR International and are tested rated and certifiedinaccordancewithAHRIStan dard 210 240 2008 and UL 1995 Due to ongoing product development product designs and specifications may change without notice Please contact the factory for more information Contents 2 Read Before Proceeding 3 Verify Unit Before Installing 4 Piston Orifice Replacement when required 7 Mounting the Unit 8 Condensate Piping 13...

Page 3: ...e explosion or electrical shockcausingpropertydamage personal injury or death Safety Instructions This manual is intended as an aid to quali fied service personnel for proper installa tion operation and maintenance of the EMI Series high efficiency air handler Read these instructions thoroughly and carefully before attempting installation or operation Failure to follow these instructions may resul...

Page 4: ...ndlers are backed by ECR International Inc and are tested rated and certified in accordance with AHRI standards 210 240 2008 and UL 1995 Verify Unit Before Installing Standard features CACG CAHG CAHJ units G or J units require a remote thermo statforoperation Theydonotincludean onboard controller External thermostat required CACH CAHH CAHK units H or K units include an on board microprocessor cont...

Page 5: ... serviceable fixed orifice expansion device and use R410A refrigerant only Controls and Components factory installed or supplied Connections for 24V wall thermostat Customcontrolboardfeaturingprogram mability configuration and multiple modes of operation CACH CAHH CAHK only Controls also feature anti short cycle timer post purge fan relay and an on board 30 amp electric heat relay Condensate pump ...

Page 6: ...the compressor should the pump become blocked or fail Important Totalliftforthispumpis36 0 9 m or less Air vanes Air outlet vanes are manually adjustable on the models 9 and 12 or driven by an electric motor on the models 24 and 36 Wherefitted themotorizedairvanescan be set to auto sweep or can be stopped in a fixed position Heating The cassette may be fitted with electric heaters which are equipp...

Page 7: ... and chart as follows Replacing the piston orifice Diassemble the orifice joint remove the factory installed orifice and replace with the 1 orifice listed in Figure 1 Supplied in the Kit Bag Make sure the o ring is in good condition and properly installed 2 Piston orifice replacement Figure 1 To Air Handler Model Condenser Factory installed orifice size Inches Replacement orifice size Inches CAHG CAHH...

Page 8: ...0 3 8 3 4 36 3 8 3 4 NOTICE Piping may be roughed in before wall board or panels are placed in new con struction PVC pipe 3 or 4 I D may be used as a pipe chase Unpacking TheCassettefasciaandmainchassisarepack aged together for increased protection Remove the banding straps and lift the 1 cardboard lid Fascia is packed in bubble wrap and on 2 top of the chassis fascia is not attached to the chassi...

Page 9: ...on adjacent sides may be blanked off If the fascia discharge slot needs blanking off Remove the inlet grilles and filters see 1 Figure 2 Page 9 and Figure 3 Page 9 Once the grilles and filters are removed 2 turn the fascia over so the polystyrene insulation is exposed Figure 4 Page 9 Push one of the polystyrene blanking off 3 pieces into the recess in the polystyrene fascia insulation Models 9 12 o...

Page 10: ...ereshouldbeaminimum1 25 4mm 8 clearance above the depth of the cassette and the false ceiling for proper installa tion See Figure 5 Page 10 See the cassette dimensions in the back of this manual for cabinet sizing Spacing requirements Figure 5 Dimension A 1 minimum space above the false ceiling for installation A A 1 Model Dimension A 9 12 11 84 0 3 m min 24 12 55 0 32 m min 36 14 51 0 37m min Wal...

Page 11: ... em bedded bolts For previously built concrete slabs install hanging bolts with an expan sion anchor Follow local building codes for required safety cables braces etc Ceiling opening NOTICE Make sure the ceiling grid is supported separatelyfromtheCassette Theceiling mustnotbesupportedbyanypartofthe Cassette unit fascia or any associated wiring or pipe work Cut an opening in the false ceiling with ...

Page 12: ...s as shown in Figure 8 Page 12 Secure the unit in position with locknuts 6 and washers on either side of the cassette bracket Ensure threaded rod does not protrude 7 more than 2 51mm below the mount ing bracket see Figure 9 Page 12 NOTICE If the ceiling is not level or even it is important that the cassette is installed level to ensure correct pump operation and to maintain fan clearances Place a ...

Page 13: ...alve at the pump dis charge to prevent water from draining backintotheunit Thispipingtechnique will minimize any issues should the check valve become stuck open from airborne debris Condensate pipe work should slope 3 downwards in the direction of water flow with a minimum gradient of 1 per 10 8mm 1m There must be no uphill gradientsotherthaninthefirst36 0 9m of pipe work from the cassette Whenmul...

Page 14: ... with unit size Branch duct knock outs are 5 133mm round Fresh air knockouts are 1 x2 32x64mm rectangular on models 9 12 3 76mm square on models 24 and 36 Cut the black insulation around the 2 knock out Figure 13 Page 14 Snip the tabs holding the knock out in 3 place Figure 13 Page 14 Remove the metal knock out and the 4 black insulation behind it Attach the duct collars field supplied to 5 the ch...

Page 15: ...th sharp edges Wrap refrigeration valves with a wet rag heat sink to protect valves while brazing See Figure 16 Page 16 DONOTuseasuctionlinesizelarger than the condenser service valve con nection This can harm the compres sor Install a reducer when used only on the inside connection NOTICE ThecassetteisequippedwithaFloRater piston expansion device Connections are sweat type Piping connections at u...

Page 16: ...etal Brazetubingintofittings usingacontinu 3 ous nitrogen purge The suction line must be insulated the 4 entire length with closed cell foam tube insulation Do not insulate the liquid line 5 Connect the outdoor unit according to 6 the instructions supplied with unit NOTICE Maximumequivalentpiperunshould 1 comply with Table 1 Page 8 Horizontal pipe runs should be 2 slightly inclined so as to encour...

Page 17: ...10A refrigerant Add and 4 remove only liquid never vapor Chargetoproperweight chargebasedon 5 feet of interconnect Figure 19 Page 17 See tables on page 18 CAUTION Refer to the charts in the condenser manual to fine tune the refrigerant charge CAUTION Charging should be done with a dial a charge or weighed in with a scale WARNING It is illegal to discharge refrigerant into the atmosphere Use proper...

Page 18: ...2 25 oz ft 23 g m 45 25 oz 1282 g S1CG3 CAC_36 64 oz ft 59 g m 97 5 oz 2764 g 18 000 Btuh CAH_24 64 oz ft 59 g m 96 75 oz 2742 g S1CG6 CAC_36 64 oz ft 59 g m 80 0 oz 2267 g 24 000 Btuh CAH_24 64 oz ft 59 g m 78 5 oz 2225 g S1HG9 CAH_09 25 oz ft 23 g m 51 52 oz 1460 g Side Discharge Multi zone S1HG2 CAH_12 25 oz ft 23 g m 45 75 oz 1296 g Circuit capacity Wall Unit Paring Line charge per foot Factor...

Page 19: ...plug by plugging it into the socket connection on the chassis Ensure that the polarized connector a 2 position is in the proper orienta tion and connected Route the wires in a way that ensures b they won t become trapped cut bro ken or chaffed ONLY Cassette H or K models 5 CACH CAHH CAHK containasec ond cable connection to the control box for the Infrared Unit Mount Control Ensure that the polariz...

Page 20: ... plug into Figure 23 socket on chassis Female vane motor plug on chassis Male vane motor plug on fascia Connect infrared unit cable H Figure 24 or K units only Red stripe is Conductor 1 Polarized 10 Position Connector Secure fascia to chassis Figure 25 CAUTION DO NOT over tight en the bolts This could cause damage tothefasciaanddrain pan Adjust louver position to 30 Figure 26 from plumb ...

Page 21: ...e maximum load current under non fault conditions at the stipulated voltages Avoid large voltage drops on cable runs 3 particularly in low voltage wiring The correct cable size must be used to 4 ensure a voltage drop of less than 1 volt in the control wiring Once the refrigeration pipe work is 5 complete the electrical supply can be connected Low voltage wiring must be at least 6 18 awg Connect wi...

Page 22: ...geinterconnectwiringmust be at least 18 AWG The24Vcontroltransformerislocatedin 1 theairhandler Thisprovideslow voltage controlpowertoboththeairhandlerand condenser Depending on the models selected the low voltage interconnect control wiring may be different Refer to the wiring diagram to connect 2 the low voltage wiring to the appropriate terminals Once the connections are made replace 3 control ...

Page 23: ...ol thermostat Ifyouhaveselectedanoutdoorheatpump unitandanindoorunitwithelectricheat then chose a two stage heating single stage cooling thermostat Field supplied thermostats When selecting a thermostat other than one offered by EMI it is important to choose a 24V thermostat that matches your applica tion EMI equipment is compatible with most mercury bulb digital or power stealing ther mostats Coo...

Page 24: ...r fan will cycle with the call for heating or cooling CACH CAHH CAHK units only The indoor unit utilizes a two speed motor For wall Thermostat Operation fan speed selec tion can be made through the DIP switch settingslocatedonthemaincontrolboard By settingDIPswitch 3RemoteThermostatFan Speed Selection to ON the fan speed will be set to High Switching to OFF the fan speed is set to Low COOLING oper...

Page 25: ...otection Optional HEAT PUMP WITH ELECTRIC HEAT Two stage heating For wall thermostat operation for two stage heatingincludingaheatpumpcondenserand indoor electric heat the control must first be configured properly Remote Thermostat ON Table 6 pg 32 Heat Source ON Figure 36 pg 35 The wall thermostat will control the call for electric heat operation on or off through the low voltage terminals R and ...

Page 26: ... is off before proceeding Perform complete inspection NOTICE To perform a system electrical check Turn off all power to the indoor and outdoor units Isolate the compressor to prevent it from operating until the check is completed by removing the con nection at the Y terminal on the outdoor unit Remove any tools or other obstructions 1 Inspect all electrical connections 2 Separate any lines that co...

Page 27: ...rge louvers are correctly positioned NOTICE Theunitisequippedwithasafetyswitch that will activate the pump when the condensate reaches a critical level The safety switch will also de energize the compressor if the water level becomes too high Check cooling operation Cooling onlysystems Turnthesystem 1 power on and turn down the system set point to activate the compressor Check heat pump operation ...

Page 28: ...r on the unit mounted display Turn on power to the indoor unit so the 3 controller can be operated Press and hold both the MODE and 4 PROGRAM buttons on the remote for 5 seconds to enter Configuration mode as shown in Figure 35 Page 34 Configure the controller using 5 Figure 36 Page 35 After the configuration is completed 6 pointtheremoteatthecassetteunit sdis play Then press and hold the POWER NOT...

Page 29: ...l setpoint above 3 room temperature Verify that the compressor shuts down 4 Wait for the blower post purge to com 5 plete Then verify that the system shuts down properly Be sure to return DIP switch 1 Test 6 mode to NO before leaving the system Verify cooling only operation This arrangement uses a cooling only 1 outdoor unit with no heat source in the cassette indoor unit The configuration 2 Figur...

Page 30: ...mperature at the cassette unit The compressor should come on Verify 5 that supply air is cooler than room air Usetheremotetoadjustsetpointtemper 6 ature1 Fabovetheroomtemperature at the cassette unit or just enough needed to activate first stage heating The compressor should come on 7 Verify that supply air is warmer than 8 room air Increase the setpoint until the second 9 stage heating electric h...

Page 31: ...r Controller Overview EMI unit mounted microprocessor controller control panel Figure 33 Dip switches Control panel WARNING Electrical shock hazard Before removing the control box cover make sure that all power is re moved from both the indoor cas sette unit and outdoor condenser unit Failure to comply could result in severe personal injury or death ...

Page 32: ... and off repeatedly in Test mode This will damage the compressor DO NOT leave the unit in Test mode after setup Return dip switch 1 to the OFF position for normal operation OFF OFF Disables Test mode 2 Louver oscillation for wall thermostat mode only ON If DIP Switch 4 is ON enables louver oscillation during operation OFF OFF If DIP Switch 4 is ON disables louver oscillation during operation 3 Fan ...

Page 33: ... In Wall Thermostat mode on when power is applied to the unit In Infrared Controller mode on while the cassette unit is in the ON mode off while unit is in the OFF mode 3 Cooling LED On when the unit is in cooling operation 4 Heating LED On during calls for heat 5 Timer Alarm LED On steady while the unit is in Sleep Timer mode flashes to indicate fault codes 6 Clear Filter warning button Hold for ...

Page 34: ...tpoint temperature Configuration Set Time or Programming mode press to increase the setting DOWN Normal operation press to decrease the setpoint temperature Configuration Set Time or Programming mode press to decrease the setting FAN Press to toggle between fan modes High Low or Auto PROGRAM Normal operation Press to toggle between manual operation and Pre programmed 7 day run mode Configuration S...

Page 35: ... built for heat pump operation and connected to an appropriate compressor unit Auto changeover differential see Note 2 04 d b x 2 6 2 Auto changeover automatically operates the unit in heating or cooling based on room temperature versus setpoint This setting is the dead band temperature Cooling is on while room temperature is at setpoint PLUS dead band Heating is on while room temperature is at set...

Page 36: ... mode 7 Day programming use Table 7 Page 37 to record settings Day of week Mon Tue Wed Thu Fri Sat Sun The louver is closed when the fan is off Period of day Morning Day Evening Night The periods provide four time settings to initiate a change in cooling heating setpoints They allow adjustments for setback such as night setback daytime setback and occupied settings for residential applications Set...

Page 37: ...n using 7 day programming Table 7 Night Cool Heat Auto Evening Cool Heat Auto Day Cool Heat Auto Morning Cool Heat Auto Time Temp Time Temp Time Temp Time Temp Time Temp Time Temp Time Temp Monday Tuesday Wednesday Thursday Friday Saturday Sunday To copy the settings from any day to the entire week 1 Select the day to be copied 2 Simultaneously press the FAN and PROG buttons for three seconds ...

Page 38: ...hesamemode This can happen if commands are entered into the remote but it is not pointed at the cassette To re synchronize Enter any command into the remote while pointing it at the cassette s infrared receiver window Alternatively hold the POWER SEND buttonfortwoseconds Alloftheoptional remote ssettingswillbetransmittedtothe cassette The cassette will respond with a beep indicating that it has su...

Page 39: ...de In Fan mode either HIGH or LOW will appear on the LCD Fan Operation The indoor unit utilizes a two speed motor with three operational fan modes High Low and Auto The FAN button will allow the selection of the desired fan setting in all modes except Dry mode In Dry mode the fan will operate constantly at low speed The LCD will indicate the fan speed selection High and Low are constant fan settin...

Page 40: ... the cooling has cycled off or fol lowing a power outage the compressor will not restart for at least three minutes anti short cycle timer Heating mode Optional Electric heat operation Air Conditioning unit outdoors For operation with electric heat the control must first be configured properly Heat Source ON Table 6 pg 32 Heat Pump OFF Figure 36 pg 35 For electric heat operation first turn the uni...

Page 41: ...he compressor will switch off The fan will operate as described in Fan 9 Operation see pg 39 Optional Heat pump with Electric heat 2 stage heating For heat pump operation with electric heat the control must first be configured properly Heatsource ONTable6 pg 32 Heatpump OFF Figure 36 pg 35 For heat pump operation with optional elec tric heat turn the unit on via the POWER SEND button ThenselectHea...

Page 42: ... If the room temperature is greater than 7 the setpoint temperature by more than two degrees the unit will run Cooling mode constantly If the room temperature is within two 8 degrees of setpoint the unit will cycle cooling on seven minutes and off seven minutes to remove humidity from the air while not over cooling the room If the room temperature is less than the 9 setpoint temperature by more th...

Page 43: ...en the PROGRAM 2 CLOCK buttons are pressed simultane ouslyagainorleftidlefortwentyseconds the control will save the new settings and return to the previous interface mode While in the 7 Day Programming mode 3 the words 7 DAY PROGRAM are dis played on the LCD Use the UP or DOWN ARROW buttons 4 tochangethetime temperatureorperiod settings Use the 5 CLOCK or PROGRAM buttons to select the mode to be c...

Page 44: ...n 7 Day Programming mode Clean Filter Alarm To aid in filter maintenance the cassette con troller will indicate when a scheduled filter cleaning is required by flashing the Timer Alarm LED During normal operation the microprocessor will keep track of the units run time When the clean filter time has elapsed 1 the Timer Alarm LED will flash four times to indicate that the filter needs to be cleaned...

Page 45: ...nd 2 the call for heating or cooling has been removed the indoor fan will remain on for an additional sixty 60 seconds This increasesefficiencybypullingtheremain ing energy from the unit Some thermostats are equipped with an AUTO ON fan switch When this switch is placed in the ON position the fan will run continuous WhentheswitchisintheAUTO position the fan will cycle with the call for heating or ...

Page 46: ...he system switch in Heating mode Adjustthesetpointtemperatureabovethe 8 room temperature The compressor and fan motors will start 9 and heating will begin Depending on the thermostat selected 10 electric heat will also energize when the deviation between room temperature and setpoint temperature is high enough to call for second stage heating See the thermostat owner s manual for this feature Plac...

Page 47: ...and can be set in the Configuration By selecting OFF the backlight will re main off at all times ByselectingON thebacklightwillremain on at all times including while in the Off mode interface If Intermittent is selected the backlight will remain for 10 seconds after the push of any button while the control is in the On mode or after the push of the ON OFF button while in the Off mode interface Dra...

Page 48: ... indoor coil If a freeze condition is detected continuously forthree 3 minutes theTimer AlarmLEDwillflashthree 3 timestosignifythatafaulthasoccurred Thecompres sorwillswitchoffforaminimumofthree 3 minutesAND until the fault condition is corrected Also if the micropro cessordetectsacoilfreezeconditionfour 4 timeswithina 24 hour period the clean filter indicator will appear 4 Clean filter To aid in ...

Page 49: ...r the retaining clips Figure 39 Page 49 Lift the filter off the grille Place filter c onaflatsurfaceandvacuumanyaway dust and debris vacuum all filters and grills Also vacuum any acces sible parts on the unit Figure 40 Page 49 Or use a garden hose d Wash the grille and filter with a hose Let filters and grilles dry before replacing Replace filters clips and front grille e before operating the unit...

Page 50: ...tewith EMI condensers The air handle indoor unit and con denser outdoor unit must be indepen dently connected to the electrical service panel and protected by separate time delay fuse or HACR breakers See the unit name plate for the correct breaker type and size The indoor and outdoor units are also connected to each other via a 24V inter connect wiring Figure 42 Page 51 or Figure 43 Page 51 A tra...

Page 51: ...tenance Manual P N 240008108 Rev G 07 08 10 51 Troubleshooting General continued Models CACG CAHG CAHJ Low voltage interconnections wall thermostat Figure 42 operation Models CACH CAHH CAHK Low voltage interconnections with without Figure 43 optional wall thermostat operation ...

Page 52: ...rminals Y and C of the outdoor unit Y1 and C of the cassette G and C of the cassette fan signal Heat pump units Heatpumpunitsrequire18AWGlow voltage interconnectingwirebetweentheindoorand outdoor units Also interconnect wiring is required between the indoor unit and wall thermostat Refertolow voltageinterconnect diagram Figure 42 Page 51 for low voltage connections The wall mounted thermostat will...

Page 53: ...affect the amp draw of the heater 5kW 22 7 A 3kW 13 6 A 1 5kW 6 9 A Theelectricheatrelaycanalsobeverified 4 by placing a voltmeter across the high voltage relay output terminal and the incoming power L2 terminal Iftheunitisworkingcorrectly thereading 5 shouldbethesameasmeasuredacrossthe incoming power supply As a safety feature an auto reset limit switch is located on the heater assembly The limit...

Page 54: ...e To check for a low voltage signal place a voltmeter across terminals Y and C of the outdoor unit Y1 and C of the cassette When the unit is working correctly there should be a reading of 24 Vac Next place the setpoint further above room temperature to activate second stage heat ing Electric heat will energize along with 1 the compressor when the deviation between room temperature and setpoint tem...

Page 55: ...e is satisfied there will be a three minute delay before the out door unit is allowed to restart The cassette controller or wall thermostat will also control the indoor fan by switching high voltage power to the fan motor with the fan relay When energized high voltage power can be measured between the relay output and the L2 terminal of the incoming power supply Foroptionalwallthermostatoperation ...

Page 56: ...hen the room temperature reaches setpoint temperature the heat cool call is dropped The fan will then stay on for an additional 60 second to purge unit of any residual energy Placing the fan selection switch on the wall mounted thermostatintheONpositionwillcause thefantoruncontinuouslyregardlessof the set point temperature Q What causes my indoor unit to freeze up A Air handler freeze up is usuall...

Page 57: ...cturedwitha low voltagetransformerinstalled When connecting an EMI air handler to a non EMI condenser check to ensure that there is no 24v control transformer in the outdoor unit Only one transformer is required If both the indoor unit and outdoor unit contain a transformer one must be removed from the system Frequently Asked Questions continued ...

Page 58: ... Page 59 NOTICE Due to ongoing product development designs specifications and performance are subject to change without notice Please consult the factory for further information Features 1 Optional discharge knockouts 5 inch diameter 3 available 2 Fresh air inlet knockouts 1 x 2 inches 9 12 2 available 3x3 24 36 3 Condensate dis charge inch diameter 4 Suction connection 5 Liquid connection 6 Conde...

Page 59: ...90 226 8 90 226 J ref 2 67 68 3 38 86 3 38 86 K 25 86 657 35 61 904 47 78 1214 L 12 76 324 18 69 475 24 73 628 M 1 73 44 1 97 50 1 97 50 N ref 2 16 55 2 72 69 2 72 69 O 5 12 130 5 12 130 5 12 130 P ref 11 34 288 12 05 306 14 01 356 R typical 1 50 38 1 63 41 1 63 41 R1 19 50 495 29 19 741 29 19 741 R2 23 27 591 31 20 792 42 66 1084 R3 22 47 571 30 41 772 43 45 1104 S 7 19 183 6 87 174 6 87 174 T 3 ...

Page 60: ...al data Table 11 Refrigerant Type R410A CONNECTIONS Model 9 12 24 36 Suction Liquid Condensate Drain I D I D I D Branch Duct 5 Ø 5 Ø 5 Ø Fresh Air Duct 1 x 2 3 x 3 3 x 3 FILTRATION Model 9 12 24 36 Type Washable Mesh Quantity 1 2 3 Efficiency 80 CONDENSATE PUMP Model 9 12 24 36 Maximum Head 36 0 9 m Min Flow Rate 2 5 GPH 9 5 l h Must bush down to 5 8 interconnect for 18K system Measured from bottom ...

Page 61: ...C_36 36 000 13 0 0 72 11 5 R410A S2CH9900 2 2 CAH_09 18 000 13 0 0 76 11 5 R410A S2CH9200 1 1 CAH_09 1 CAH_12 21 000 13 0 0 72 11 5 R410A S2CH2200 2 2 CAH_12 24 000 13 0 0 68 11 5 R410A Heat pump systems Table 14 CAH_ refers to CAHG CAHH CAHJ CAHK Condenser Cassette Cooling Btuh Heating Btuh SEER HSPF SHR EER COP Ref S1H9000 CAH_09 9 000 8 200 13 0 7 7 0 74 11 8 3 2 R410A S1H2000 CAH_12 12 000 9 6...

Page 62: ...3 0 410A T3HG9990 3 CAH_09 28 400 24 000 13 0 7 7 0 77 11 5 3 1 410A T4HG2222 4 CAH_12 48 000 32 800 13 0 7 7 0 70 11 5 3 0 410A T4HG9922 2 CAH_09 2 CAH_12 42 900 29 400 13 0 7 7 0 75 11 5 3 0 410A T4HG9992 3 CAH_09 CAH_12 39 600 33 200 13 0 7 7 0 75 11 5 3 0 410A T4HG9999 4 CAH_09 36 000 32 000 13 0 7 7 0 77 11 5 3 1 410A Straight cool systems with cassette units _ Table 16 _ G H J or K Condenser...

Page 63: ... Fan Motor Volts ID Fan Motor Amps Total Volts Total Amps Temperatures Degrees F Compressor Suction Compressor Discharge Liquid Out Cond Liquid before Expansion Suction out Air handler Capacity Calculations DB Temp Split at Air handler Test Summary Compressor Superheat Sub Cooling Test Unit Performance Data Sheet NOTICE The Test Unit Performance Data sheet is provided for use by a qualified servic...

Page 64: ...rge S2CH S2HH Dual Zone Side Discharge WLCG WLHG High Wall Air Handler UNCG UNHG Universal Floor or Ceiling Air Handler CACG CAHG CAHJ Cassette Air Handler S1CG S1HG hone 1 800 228 9364 ax 1 800 232 9364 220 20 220 220 2201 D 1 D 1 D 1 D 1 Dw w w wy wy wye yer Av Uti Utica ca NY NY 1350 T2CG T2HG T3CG T3HG and T4CG T4HG 2 3 and 4 Zone Top Discharge ...

Reviews: