ECR International 18k Installation, Operation & Maintenance Manual Download Page 15

Air and moisture in the refrigerant system have undesirable effects as indicated below:

Pressure in the system rises.

Operating current rises.

Cooling or heating efficiency drops.

Moisture in the refrigerant circuit may freeze and block capillary tubing.

Water may lead to corrosion of parts in the refrigeration system.

Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested
and evacuated to remove any noncondensables and moisture from the system.

Air purging with vacuum pump

Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units
have been properly connected and all wiring for the test run has been completed. Remove
the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both
the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

Pipe length and refrigerant amount:

Connective pipe length

NOTE:  N=2(one-twin models), N=3(

), N=4(one-four models), N=5(one-five models).

             The Standard pipe length is  7.5m(25ft). 

one-three models

Pre-charge pipe length(ft/m)
(Standard pipe lengthxN)

More than (Standard pipe lengthxN)ft/m

Air purging

method

Use vacuum
pump. 

Use vacuum
pump. 

Additional amount of refrigerant to be charged

              (R410A)

 AIR PURGING

Air purging

1

5

Liquid sid

e:        6.

35(1/4

"

)     

(Total pipe length - standard pipe lengthxN)x15g(0.16o

z

 

)/m(ft)

 

Liquid sid

e: 

       

9.52(3/8 ") 

(Total pipe length - standard pipe lengthxN)x30g(0.32o

z

)/m(ft)

When relocate the unit to another place, perform evacuation using vacuum pump.

Make sure the refrigerant added into the air conditioner is liquid form in any case.

Open the valve stem until it hits against the 
stopper. Do not try to open it further.
Securely tighten the valve stem cap with a
spanner or the like.
Valve stem cap tightening torque (See 
Tightening torque table in previous page ).

Outdoor
unit

Indoor
unit

Refrigerant 

Flare nut

Stopper

Cap

Valve body

Packed valve

Half union

Gas side

Liquid side

A

C

D

B

Valve stem

Fig.

1

6

Fig.

1

7

   

Caution in handling the packed valve

When Using the Vacuum Pump

(For method  of using a  manifold valve, refer 
to its operation manual.)
1. Completely tighten the flare nuts, A, B, C, D,
    connect the manifold valve charge hose to a 
    charge port of the low-pressure valve on the 
    gas pipe side.
2. Connect the charge hose connection to the

vacuum pump.

3. Fully open the handle Lo of the manifold valve.

Summary of Contents for 18k

Page 1: ...s Split System Heat Pumps Installation Operation Maintenance Manual ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Phone 800 325 5479 Web enviromaster com 18k 27k 36k 45k PN 615000159 REV B 01...

Page 2: ...manual are subject to change without prior notice for product improvement The actual shape should prevail Contact an authorized service technician for repair or maintenance of this unit The appliance...

Page 3: ...rnal force will be acted on the terminal If connection or fixing is not perfect it will cause heat up or fire at the connection 7 Wiring routing must be properly arranged so control board cover is fix...

Page 4: ...door unit to prevent direct sunlight or rain exposure More than 11 8 in 30cm make sure that heat radiation from the condenser is not restricted Ensure that the clearance around the back of the unit is...

Page 5: ...g Hitch it on the connective cable between indoor unit and outdoor unit after installation Cord protection rubber ring If the cord clamp can not fasten the cord for the small size of the cord please u...

Page 6: ...Two of the A B and C directions should be free from obstructions INSTALLATION INSTRUCTIONS 6 CAUTIONS One Two One Three One Four More than 4 72 in 12cm Air filter Remote controller Air filter Remote c...

Page 7: ...supporting should be taken The connection between bracket and wall bracket and the air conditioner should be firm stable and reliable Be sure there is no obstacle to block flow Strong wind Fig 4 Outdo...

Page 8: ...put them on after flaring work Flare nut Copper tube Fig 9 8 REFRIGERANT PIPE CONNECTION 1 2 Drain joint installation NOTE The drain joint may differ from appliance to appliance Fit the seal into the...

Page 9: ...ent protection device and disconnect switch should be used for each unit 4 Ensure the air conditioner is grounded well 5 Refer to the attached Electrical Connection Diagram located on panel of outdoor...

Page 10: ...wires or power cords are connected reliably and correctly or the air conditioner could not run normally Fig 15 CAUTIONS Make sure to connect the indoor unit A B C D E to the Hi and Lo valve and termin...

Page 11: ...A L B N A N B S A S B Model C TO A POWER POWER POWER POWER POWER POWER TO B L N S L1 L2 S 1 2 3 L1 L2 S 1 2 3 L1 L2 S L1 L2 S L1 L2 S 1 2 3 L1 L2 S 1 2 3 L1 L2 S L1 L2 S L 1 1 2 N S L 1 1 2 N S L N S...

Page 12: ...L1 A L1 A 1 A L2 A L2 A 2 A S A S A 3 A L1 L1 L1 L2 L2 L2 L1 L2 S 1 2 3 1 2 3 L1 C L1 C 1 C L2 C L2 C 2 C S C S C 3 C L1 B L1 B 1 B L2 B L2 B 2 B S B S B 3 B L1 L2 S 1 2 3 1 2 3 L1 L2 S 1 2 3 1 2 3 L...

Page 13: ...2 N S TO C L 1 1 2 N S TO D L 1 1 2 N S TO B L 1 1 2 N S TO E L 1 1 2 N S Model C POWER L N L A N A S A L B N B S B L C N C S C L D N D S D L E N E S E Model D TO B TO C TO A TO D W 1 L 2 N S W 1 L 2...

Page 14: ...as specified in the power source specification 7 Always install an ground fault circuit breaker in a wet or dump area 8 The following would be caused by voltage drop Vibration of a magnetic switch whi...

Page 15: ...pe length ft m Standard pipe lengthxN More than Standard pipe lengthxN ft m Air purging method Use vacuum pump Use vacuum pump Additional amount of refrigerant to be charged R410A AIR PURGING Air purg...

Page 16: ...um valves and the vacuum position is at the main valve the system is not connected with the indoor unit must be tightened with a screw nut Checking the gas leakage before operation to prevent leakage...

Page 17: ...k at the flare nut connections and electrical safety check Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open 1 Connect the...

Page 18: ...Controller at the Indoor Unit for steps 6 and 7 6 Install batteries into Wireless Remote Controller 7 Immediately press and hold MODE FAN and TIMER ON button for 3 seconds until Wireless Remote Contr...

Page 19: ...NOTES...

Page 20: ...CS464 I 16122000001504 20150912 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Reviews: