ECP240R

RATINGS:
Voltage:

 

  US/CA:  120/240V~, 2W + N + PE,  

   

60Hz, 2.7A

  International:  240V~, 50Hz, 2.7A

Configuration:

 

  3-wire plus ground (US) 

  2-wire plus ground (International)

Capacitance: 

  30µf (US)

Line Current: 

  2.7 A

KVA Rating: 

 

.65 at 240V AC

TeST pRoCeduReS:

1.   Energize the power panel.
2.   Close the circuit breaker leading to the 

EcoPower4™ unit.

3.   Check if Line 1 and Line 2 indicator lights 

are on: 

IF NO - De-energize the unit and check if 

cables are connected correctly. 

 

NOTE: For international appliances, only 

1 indicator light may be on.

 

Check the ground cable connections.

 

If problem persists, call EcoTrust Energy 

at 1.800.989.2299.

4.  Keep these instructions near the unit for  

future use.

EcoPower4

ECP240R

LINE

RED

BLACK

GREEN

WHITE

L1

L1

L2

L2

NEU

BUS

GND

BUS

20A

BREAKER

POWER PANEL

LINE

BROWN

GREEN WITH YELLOW STRIPE

BLUE

L

L

NEU

BUS

GND

BUS

20A

BREAKER

POWER PANEL

EcoPower4

ECP240R

US/CANADIAN INSTALLATION

INTERNATIONAL INSTALLATION

3.   Run conduit (according to code) between the conduit connector on the box and the 

power panel, and feed the connection cables through the conduit into the power 

panel.

instaLLation ProcedUres:

1.   If possible, de-energize the power panel prior to connection of the EcoPower4™ 

unit.

2.   Install the circuit breaker onto the power panel.
3.   US/Canadian  Installation  -  Connect  the  (red)  L1  and  (black)  L2  wires  to  the  circuit 

breaker, the ground cable (green) to the ground bus, and the neutral cable (white) to 

the neutral bus, as shown in the diagram below.

4.   International Installation (240V, 50Hz) - Connect the brown wire (hot) to the circuit 

breaker, the ground wire (green with yellow stripe) to the ground bus, and the blue 

wire to the neutral bus as shown in the diagram below.