© Ecotec Heat Pumps Ltd
|
Installation Manual & User Guide
4
The heat pump and floor stand must be positioned
on a solid level surface. Avoid installing the heat
pump close to sensitive walls such as bedroom
walls, since the pump produces a limited amount
of noise and vibration when running.
Protection
The unit is designed for outdoor use and exposure
to the elements including direct sunlight. It is
advisable to shelter the unit from strong wind, and
snow drifts. Falling snow or ice from eaves can
damage the unit so it is recommended that a roof
be installed for added protection.
Ventilation
Proper ventilation around the unit is important so
it should not be placed in small enclosed spaces
or rooms that could restrict the fresh air supply to
the unit. Proper clearances should be maintained
around the heat pump so that air can flow freely
through the heat exchanger.
minimum distance from a wall is 30 cm (12”)
If multiple units are installed side by side,
minimum recommended space between units
is 40cm (16”)
Free space in front of the unit 3m
Drainage
The heat pump produces water from condensation
and the defrosting process. Installing it close to
pathways or staircases should be avoided because
of the risk of slip hazards from ice buildup.
Condensation in humid climates can be in excess
of 30 liters per day so proper drainage around the
unit is important.
Placement checklist
Units should be placed outdoors for
unrestricted air supply.
Do not install the unit in areas where smoke
or gases collect
Do not install the unit in extremely damp or
steamy areas.
Do not install the unit in areas where
excessively high heat-producing equipment is
located.
Locate the unit close to the hot water storage
cylinders / usage areas to reduce piping and
heat loss.
The unit must sit level, the use or footings or
a raised plinth is recommended.
Units with tanks sit on frame footings, care
should be taken to elevate units in case of
flooding.
Units can sit freely on a hard flat surface
provided it can maintain the weight of the
unit.
Units without tanks may be wall mounted
using load rated metal brackets or floor
mounted.
Side and front panels should be easily accessible
allowing for periodic cleaning. (See maintenance
guide)
Do not to block the air intake vents which are
located on the rear of the unit. Minimum
clearance is 30 mm (12”) between the air
intake and wall to allow for proper air flow.
Avoid locations that cause recirculation of
cold air exhaust, since this reduces the heat
output.
Outdoor pipes must be well insulated to
prevent heat loss and freezing.
Locating the heat pump