5 |
P a g e
REMOVING
BLOWER/CONTROL
ASSEMBLY
Blower and control assembly can be removed as a single piece:
•
Turn off power to
ecosmart
•
Disconnect AIR OUT temperature sensor (white plug/socket) just above front centre
plate
(8)
and pull up out of the way to prevent damage to the cable when sliding out
assembly
•
Disconnect power, thermostat and other wiring from within control box
(1, 2, 3, 4, 5, 6,
7)
•
Undo (Qty. 2) #1/4-20 bolts, lock washers and flat washers
•
Slide out blower assembly
TROUBLESHOOTING
Smart/WiFi thermostat not working properly
Standard digital thermostats usually have internal batteries and do not require external power.
Smart thermostats require a constant source of external power to operate internal electronics.
This power is derived from a ‘C’ connection that is available
at all times
. Do not use the ‘C’
connection intended for the condenser
(3)
as this is switched on only when the outdoor
condenser runs. Use a constant ‘C’ connection derived from the 24VAC transformer
(15)
connected as follows: