background image

 

Range 2 

– MB18 

Operating instructions

 

 

ECOSAFE | Date du document : 29/04/2019 – Version : 01 

 

1.  DESCRIPTION / USE 

 

Flammable products have to be stored in safety cabinets. These safety cabinets are compliant to the standard FM and to the NFPA 

– 

OSHA specifications with a 10- minute fire resistance. They are available with manual or automatic closing doors. 

 

2.  TECHNICAL FEATURES 

 

Compliance :  

 

Compliance  with  the  specifications  NFPA  (National  Fire  Protection  Association),  OSHA  (Occupational  Safety  and  Head 

Administration) et FM (Factory Mutual International) 

 

Technical features :  

 

Construction in 18-gauge (1-mm) thick double-wall, welded steel with 1-

1/2” (38-mm) of insulating air space 

 

Standardized pictogram for flammables provided (trilingual) 

 

One swing door 

 

Manual door, that open to a full 180 degrees 

 

3-point locking-system 

 

Shelves adjustable 

on 3” (76-mm) centers for versatile storage 

 

L

eakproof 2” (51-mm) bottom sump 

 

Dual vents with flame arresters 

 

4 self-leveling feet 

 

Grounding connector 

 

External dimensions : H 610 x W 1090 x D 460 mm 

 

Internal dimensions : H 515 x W 1005 x D 390 mm 

 

Storage capacity : 64 liters 

 

Retention capacity : 20 liters 

 

Loading capacity : 159 KG per shelf 

 

Weight : 75 KG 

 

3.  INSTALLATION AND COMMISSIONING 

 

Installation 

 

The safety cabinet has to be installed on a flat surface that can bear its weight with the products inside.  

Ensure that the safety cabinet is correctly wedged, as for the cabinet not to topple. The eventual blocking has to be done by the user.  

The correct leveling of the cabinet must cart off any distortion of the frame, allow the doors to be strictly parallel compared to the frame, 

and take away any rubbing of the doors on the cabinet’s frame.  

 

The installation location must guarantee :  

 

That it is not exposed to any heat source 

 

That it is protected against moisture and that the ambient temperature of the location is neither less than 5°C, nor more than 

40°C 

 

Summary of Contents for MB18

Page 1: ...Range 2 MB18 Operating instructions ECOSAFE Date du document 29 04 2019 Version 01 0 Instruction manual For safety cabinet Model MB18 ...

Page 2: ...ONTENT 1 Description Use Page 2 2 Technical features Page 2 3 Installation and commissioning Page 2 4 Internal equipments Page 3 5 Storage Page 3 6 Ventilation Page 3 7 Safety controls Page 4 8 Spare parts Page 4 9 Recycling Page 4 10 Warranty Page 5 11 Control sheet for the user Page 6 ...

Page 3: ...enters for versatile storage Leakproof 2 51 mm bottom sump Dual vents with flame arresters 4 self leveling feet Grounding connector External dimensions H 610 x W 1090 x D 460 mm Internal dimensions H 515 x W 1005 x D 390 mm Storage capacity 64 liters Retention capacity 20 liters Loading capacity 159 KG per shelf Weight 75 KG 3 INSTALLATION AND COMMISSIONING Installation The safety cabinet has to b...

Page 4: ...the loading capacity per shelf of 159 KG The cabinet also has an integrated retention tank which has a retention capacity of 20 liters 5 STORAGE Your safety cabinet is exclusively destined to store chemicals in laboratories industries schools in closed containers It must not store high concentrated corrosive products We remind you that the storage of corrosives can alter the quality of your safety...

Page 5: ...ded 7 SAFETY CONTROLS Your safety cabinet is a safety equipment As to guarantee its perfect efficiency you have to check the equipment regularly Daily safety controls Check if the products liquids powders have flowed in the containment sumps If it has they have to be emptied and cleaned promptly with suitable equipment absorbent mat Check that the cabinet and its internal equipments are not corrod...

Page 6: ...ouse The spare parts are under 3 months warranty upon their settlement The warranty cannot be applied in the following cases The equipment has not been stored used or maintained in accordance with the standards by the user In case of a damage of the equipment by the user or a third party The equipment had a modification or a repair by the user or a third party without any prior written authorizati...

Page 7: ...y The locking system of the doors works correctly The mechanic ventilation system is running correctly if applicable The ventilation system is not obstructed The air inlet and outlet are clean The standardized pictogram on the door is in good condition and visible The door hinges are lubricated The locking system is lubricated The containment sump is clean Remarks Date By Signature ...

Reviews: