background image

37

System Protection

8.0 ACTIVE SYSTEM PROTECTION FEATURES

The controls found in the (-)A20 condensing units 

are designed to prevent the system from operating

in under conditions that could be harmful to the

compressor and inverter. The Variable Speed

Outdoor Control (VSODC) and Power Inverter

continuously monitor multiple sensors, current,

and voltage and will modify the compressor speed

or completely shut the system down to protect the

compressor and/or inverter if harmful operating

conditions are sensed. This process is called

Active System Protection. Sections 8.1 – 8.15

give a brief description of the different forms of

protection that are provided. Refer to Section 9.4

in the Diagnostic and Troubleshooting Section

of this manual for Active System Protection fault 

codes and additional details for each fault.  

8.1 Minimum Run Timer 

A minimum run time of 30 seconds is maintained by 

the VSODC to minimize short cycling which can be 

harmful to the compressor.

8.2 Oil Return Cycle

When the system has been operating at

significantly reduced capacity for an extended 

period of time, the Variable Speed Outdoor Control 

(VSODC) will signal the Inverter to speed the

compressor up to help bring any oil that has 

accumulated in the indoor coil and refrigerant lines 

back to the compressor sump. 

8.3 Oil Dilution

During operation, it is possible for excess

refrigerant to collect in the compressor causing 

a flooded compressor sump which can dilute the 

oil and harm the bearings inside the compressor.  

The Compressor Sump Thermistor is continuously 

monitored by the Variable Speed Outdoor Control 

(VSODC).  The VSODC will evaluate the differential 

between the sump temperature and the saturated 

suction temperature (sump superheat) and signal

the Inverter to reduce the compressor speed to

increase the sump superheat level should it fall 

below a safe level.  Once the minimum acceptable 

sump superheat level is attained, the VSODU

will signal the Inverter to gradually increase the com

-

pressor speed as much as possible while

maintaining an acceptable sump superheat level 

until the compressor speed returns to normal

speed based on the capacity demand.

8.4 Off-Cycle

Refrigerant Migration -

Stator Heat

Refrigerant can migrate to a cold compressor during 

the off cycle which can dilute the oil or result

in the oil being pumped out when the compressor 

starts.  The VSODC continuously monitors the

Compressor Sump Thermistor input during the off-

cycle and when the compressor shell temperature 

drops to 45°F [7.2°C], the VSODC will signal the 

inverter to energize one of the compressor stator 

windings (Stator Heat) to generate enough heat

to warm the compressor to prevent refrigerant

migration to the compressor or boil off any refrig

-

erant that may have migrated to the compressor. If 

Stator Heat is energized in the off cycle,

the compressor is prevented from starting until the 

compressor shell temperature measured by the 

Sump Temperature Thermistor is greater than 50°F 

[10°C].

8.5 High Discharge 

Temperature

The Power Inverter continuously monitors the

Discharge Line Thermistor input to protect the

compressor should the discharge temperature

reach an unsafe level.  If the discharge line 

temperature rises to 235°F [113ºC], the Inverter

will reduce the compressor RPM incrementally

until the temperature drops to 200°F [93ºC]. After

the discharge temperature reaches 200°F [93ºC],

the Inverter will gradually increase the compressor

RPM until the compressor returns to normal

speed based on the capacity demand. Should the

discharge temperature rise to 235°F [113ºC] again,

the Inverter to repeat the speed reduction cycle to

maintain a temperature below 235°F [113ºC].

8.6 High Discharge 

Pressure

The High Pressure Control (HPC) limits the

compressor discharge pressure to a safe level to

prevent damage to the compressor. When the

HPC contacts open at 610 PSIG, the compressor

will proceed to shut down and restart per the

sequence shown below. If the HPC contacts open

three (3) times during the same call for operation,

the VSODC will lock the compressor out and will

flash a 29L fault code and the EcoNet

TM

 Control

Center will display a High Refrigerant Pressure

Lockout fault on the screen.   A manual reset is

required for the VSODC to exit the compressor

lock-out mode and clear the fault. This is

accomplished by disconnecting the electrical 

Summary of Contents for A2024AJVCA

Page 1: ...NSTALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATIO...

Page 2: ...tat 25 5 7 IndoorAir FlowVerification 26 5 8 Refrigerant Charging 26 5 8 1 Measurement Device Set Up 27 5 8 2 Preliminary Charging by Weight 27 5 8 3 Preliminary Charging by Pressures 27 5 8 4 Final C...

Page 3: ...disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components accessories or devices CAUTIONS R 410A systems operate at approximately 60 higher pressures...

Page 4: ...1 of this manual 2 3 Importance of Quality Installation A quality installation is critical to assure safety reliability comfort and customer satisfaction Strict adherence to applicable codes the info...

Page 5: ...S CONTROLS C COMMUNICATING TYPE V INVERTER VOLTAGE J 1 PH 208 230 60 MAJOR SERIES A 1st GENERATION CAPACITY 24 24000 BTU HR 7 03 kW 36 36000 BTU HR 10 55 kW 48 48000 BTU HR 14 07 kW 60 60000 BTU HR 17...

Page 6: ...NDED Rev 11 15 Electrical Fuse or HACR Circuit Breaker Compressor Rated Load Amperes RLA Locked Rotor Amperes LRA Model Number A20 Phase Frequency Hz Voltage Volts Fan Motor Full Load Amperes FLA Mini...

Page 7: ...y cylinders need to have a 400 psig 2 758 kPa service pressure rating DOT 4BA400 or DOT BW400 Combustibility At pressures above 1 atmosphere a mixture of R 410A and air can become combustible R 410A a...

Page 8: ...f other equipment installed in proximity to the unit Maintain all required minimum distances to gas and electric meters dryer vents and exhaust and inlet openings In the absence of national codes or m...

Page 9: ...r that will not wash off with water 4 2 4 Customer Satisfaction Issues The outdoor unit should be located away from the living sleeping and recreational spaces of the owner and those spaces on adjoini...

Page 10: ...mpressor Capacity losses System oil level adjustment 4 4 2 1 Oil Return to Compressor Small amounts of compressor crankcase oil is picked up and carried out of the compressor by the moving refrigerant...

Page 11: ...342E ZE9 130 ZPV038CE 2E9 130 Compressor Nameplate Oil Charge oz 40 40 40 40 4 4 2 6 Capacity Losses Long line lengths can result in a reduction in capacity due to suction line pressure drop and heat...

Page 12: ...line 4 90 LR elbows and a filter drier Fitting Equivalent Length ft 4 9 6 9 6 Total Equivalent Length ft 75 9 6 84 6 This application is acceptable because the 25 vertical rise is less than the maximu...

Page 13: ...0 99 50 0 98 50 0 97 50 0 96 4 Ton 3 8 3 4 25 0 99 50 0 98 50 0 97 50 0 96 50 0 94 50 0 93 1 2 3 4 25 0 99 50 0 98 50 0 97 50 0 96 50 0 94 50 0 93 3 8 7 8 25 1 00 50 0 99 50 0 99 50 0 98 50 0 98 50 0...

Page 14: ...15 0 99 15 0 99 15 0 98 15 0 97 15 0 96 14 1 KW 4 Ton 9 53 3 8 19 05 3 4 8 0 99 15 0 98 15 0 97 15 0 96 15 0 94 15 0 93 12 7 1 2 19 05 3 4 8 0 99 15 0 98 15 0 97 15 0 96 15 0 94 15 0 93 9 53 3 8 22 23...

Page 15: ...to form vapor insulating the liquid line is required Use clean dehydrated sealed refrigeration grade tubing Always keep tubing sealed until tubing is in place and connections are to be made A high qua...

Page 16: ...ICATIONS INSULATED SUCTION LINE FULL LENGTH REFERENCE TABLE 2 FOR MAXIMUM LENGTH LIMITATIONS Figure 3 For applications with the outdoor unit and indoor unit on the same level the following is required...

Page 17: ...nit below the indoor coil the following is required Inverted suction line trap Reference Figure 4 Insulated liquid line in unconditioned space only Follow the proper line sizing maximum linear and equ...

Page 18: ...conditioned space only Follow the proper line sizing maximum linear and equivalent length maximum vertical separation charging requirements and oil level adjustments spelled out in this document Tubin...

Page 19: ...f the tubing with a clean dry cloth before soldering Clean out debris chips dirt etc that enters tubing or service valve connections Wrap valves with a wet rag or thermal barrier compound before apply...

Page 20: ...cuation see Sections 4 7 and 4 8 for evacuation and final leak testing ST A1226 06 00 The suction line must be insulated for its entire length to prevent dripping sweating and prevent performance loss...

Page 21: ...l 24VAC 2 stage ther mostat many features and benefits are lost Therefore a conventional 24VAC 2 stage thermostat should only be used in temporary emergency situations until communication issues with...

Page 22: ...s the settings status or service icons at the bottom of the touch screen Refer to the air handler or furnace installation manual and the EcoNet Control Center installation manual for further details o...

Page 23: ...ble operating voltage range is shown below VOLTAGE RANGES Nameplate Voltage Operating Voltage Range at Maximum Load Conditions 208 230 1 Phase 197 253 Install a branch circuit disconnect within sight...

Page 24: ...wer to the indoor and outdoor units The EcoNetTM Control Center should be switched to the off position initially Within 45 seconds of power being applied the EcoNetTM Control Center should detect the...

Page 25: ...the screen and then touch Stop Test Then touch the left arrow on the screen to return to the main screen 9 If the indoor blower continues to run continuously after exiting the Charge Mode cycle the p...

Page 26: ...the installation and should be done prior to final charge adjustment NOTICE AHRI rated CFM may differ slightly from values in the table below Outdoor Unit Model No Displayed Indoor CFM Cooling Mode A...

Page 27: ...3 g or volumetric charging device adjust the refrigerant charge based on the actual line set length If the entire system has been evacuated add the total calculated charge IMPORTANT Charging by weigh...

Page 28: ...___ C as measured from a temperature probe located within 6 15 2 cm outside of the unit on the copper liquid line small line It is recommended to use a calibrated clamp on temperature probe or an insu...

Page 29: ...then direct the variable speed ECM indoor blower motor to start and operate at the requested cooling air flow level As the building load changes throughout the call for cooling operation the compresso...

Page 30: ...2nd stage operation the compressor will ramp to its full capacity speed and the RHMV air handler will deliver the maximum air flow level For gas furnace applications the variable speed gas furnace wi...

Page 31: ...densing units are equipped with a discharge line thermistor that is used to measure the compressor discharge temperature This sensor s leads connect directly to the inverter which communicates with th...

Page 32: ...cation of each 1 Thermostat Terminals 2 Communication wire terminals 3 Modbus unitary inverter communication connection 4 Outdoor PSC Fan relay connections 5 Outdoor ambient thermistor connection 6 Co...

Page 33: ...menu CS Compressor Speed For this selection menu to initiate the requested compressor speed there must be an active call for compressor operation the com pressor must be operating and the selection m...

Page 34: ...ng Filter 7 9 High Pressure Control HPC Sensing of the compressor discharge pressure is accomplished by a conventional automatic reset pressure control that is brazed into the compressor discharge lin...

Page 35: ...equency 3 phase power that is connected to the 3 phase compressor motor Each of the four A20 models has a unique inverter specifically designed and qualified for that specific model to provide reliabl...

Page 36: ...h a suction line thermistor for the purposes of measuring suction gas temperature The measured temperature is paired with the saturated suction temperature and used by the VSODC to calculate superheat...

Page 37: ...vel until the compressor speed returns to normal speed based on the capacity demand 8 4 Off Cycle Refrigerant Migration Stator Heat Refrigerant can migrate to a cold compressor during the off cycle wh...

Page 38: ...TE If the system experiences a low refrigerant pressure lock out the system should be evaluated to determine the cause for the low pressure condition and corrective action taken to eliminate the cause...

Page 39: ...the EcoNetTM Control Center and Variable Speed Outdoor Control identifying which sensor has failed See the table below for the default operation for a sensor failure FAILED COMPONENT FUNCTION DEFAULT...

Page 40: ...ol Center service menu select SERVICE on the screen and navigate to the fault code section to retrieve any fault codes that have been stored To access fault codes on the VSODC press the SW2 and TEST b...

Page 41: ...run time 30 seconds active The unit has received a command for first stage cooling during an active anti short cycle timer or minimum run timer Wait until unit timer has expired or press the TEST butt...

Page 42: ...rter Fault Compressor Overcurrent Compressor is pulling more current than allowed Compressor Shorted to Ground Check resis tance of windings to ground Wiring to compressor or molded plug damage Inspec...

Page 43: ...w 10 Flashes A907_O Inverter Fault DC Bus Undervoltage Incoming Voltage 170 VAC Verify Incoming voltage to Drive by measuring voltage at L1 to L2 Yellow 9 Flashes T908_O Inverter Fault PIM Over Temp I...

Page 44: ...nections at U V W and Molded plug Check Compressor Windings for significant differences in resistance Yellow 14 Flashes A912_O Inverter Fault Micro Fault Micro on Drive Faulted Hard Reset on Drive If...

Page 45: ...s Cable Hard Reset of Drive If fault persists replace drive Yellow 8 Flashes A921_O Inverter Fault PFC Temp Sensor Open Sensor to PFC is either low or open Verify proper airflow over the heatsink of t...

Page 46: ...reset Check fault history for cause of lockout condi tion at control center Address fault as indicated in history A929_O 240VAC Missing or Comm Failure Formerly Comm Failure Drive is either not power...

Page 47: ...VSODC Verify leads to sensor are not pinched or damaged Check sensor resistance temp A954_O Suction Tempera ture Thermistor Failure Suction Thermistor is either Open Shorted or Low Until will run in...

Page 48: ...ssure switch has opened Check Refrigerant Charge Check connection of HPS to Drive A958_O High Refrigerant Pressure System High pressure switch has opened 3 times and is locked out for one hour Check R...

Page 49: ...e When Discharge temperature exceeds 235 o F Compressor will slow down to bring discharge temperature down below 200oF Check system superheat and charge Verify reversing valve is not leaking from disc...

Page 50: ...condition in the power factor correction circuit the inverter will auto matically shut the compressor off and keep it from operation There is a 5 minute delay after this fault occurs before VSODC will...

Page 51: ...nverter will automatically shut the compres sor off and keep it from operation There is a 5 min ute delay after this fault occurs before VSODC will restart the compressor If this fault occurs 3 times...

Page 52: ...ORTANT This mode of active protection must be manually reset L15 PIM Temperature Fold back T922_O Inverter Fault If the inverter detects a high Power Module tem perature the inverter will automaticall...

Page 53: ...operation The VSODC will lock out the compressor to keep it from continuing to operate and flash an L on the dual 7 segment LEDs followed by a 16 IMPORTANT This mode of active protection must be auto...

Page 54: ...automatically shut the compressor off and keep it from operation The VSODC will leave the compressor off until the input AC voltage increases to 187VAC At this time the VSODC will restart the compress...

Page 55: ...set once the OAT sensor failure is corrected 42 Compressor Temperature Thermistor Failure T955_O If the VSODC identifies an issue with the Compressor Sump Thermistor CPT the VSODC will flash a 42 on t...

Page 56: ...ng C or H and Code Refer to the VSODC Diagnostics Codes section from this manual for fault code troubleshooting Check fault history for other faults See the VSODC Diagnostic Codes and the Active Compr...

Page 57: ...ers Dirty Indoor Coil Inadequate Indoor Airflow Inoperative Indoor Blower Low on Charge Low Ambient Temperature Bad Compressor Dirty Outdoor Coil Inoperative Outdoor Fan Overcharge Recirculation of Ou...

Page 58: ...he order of operations is called PEMDAS Parentheses Exponents Multiplication Division Addition and Subtraction Our formula doesn t have any Exponents so we can eliminate that Also there is no Addition...

Page 59: ...the resistance decreases Measurements will be made with the sensor disconnected from the control board Again comparing the results must be done against a calibrated tester A glass of water mixed compl...

Page 60: ...sized unit Refrigerant undercharge or overcharge LPC or HPC cycling At inverter input terminals voltage must be between 187 252VAC when unit is operating Adjust refrigerant charge per charging chart...

Page 61: ...rsized wire feeding unit Correct and complete diagnosis High line voltage Power company problem Report problem High head pressure Overcharge Check system charge Dirty head pump coil Clean coil Faulty...

Page 62: ...tat Check for control voltage to contactor coil Compressor control circuit High pressure switch Low pressure cut out Ambient thermostat Stater heat is active Compressor timed off on control or interlo...

Page 63: ...k system charge Refrigerant leaks Repair and recharge Cold noisy compressor Slugging Dilution of oil with refrigerant Observe piping guidelines Noisy compressor Migration Check stater heat and compres...

Page 64: ...Undersized EXV Replace with correct valve Incorrect sensing suction line temperature Verify suction thermistor resistance is correct and properly attached and insulated to the vapor line Suction ther...

Page 65: ...nsulation Low superheat adjustment Charge the superheat offset dip switches on indoor coil EXV control to increase superheat Incorrectly sensing suction line temperature Verify suction thermistor resi...

Page 66: ...Chart Overcharge High High Low High Undercharge Low Low High Low Liquid Restriction Drier Low Low High High Low Indoor Airflow Low Low Low Low Dirty Outdoor Coil High High Low Low Low Outdoor Ambient...

Page 67: ...task WARNING Disconnect electrical power to the unit before removing the top panel or any electrical panel as the fan motor could start at any time and live electrical connections will be exposed Annu...

Page 68: ...NSTALLED FACTORY OPTION FACTORY STANDARD LINE VOLTAGE ELECTRICAL WIRING DIAGRAM 90 101229 39 02 VARIABLE SPEED ECONET AC ONLY W ECM MOTOR A 1080S133 ORIGINAL RELEASE NO MODELED BY CHECKED APPROVED REV...

Page 69: ...air handler settings or furnace settings screen select N C next to the Aux Input 1 Config label e Change the Aux 1 Config type to N C by pressing the orange up or blue down arrows at the bottom of th...

Page 70: ...e the thermostat will not permit return to the home screen a To turn the unit off either press the blue down button until stop test appears at the bottom of the screen and then press stop test on the...

Reviews: