
W2W Series Heat Pump
Ecologix Heating Technologies Inc
Page
3
www.ecologix.ca
221 Holiday Inn Drive Cambridge ON
ph: 519-658-4330
General Information
Inspection
Upon receipt of the equipment, carefully check
the shipment against the bill of lading. Make
sure all the units have been received. Inspect the
carton or crating of each unit, and inspect each
unit for damage. Assure the carrier makes
notation of any shortages or damage on all
copies of the freight bill and completes a
common carrier inspection report. Concealed
damage not discovered during unloading must be
reported to the carrier within 15 days of receipt
of shipment.
If not filed within 15 days, the
freight company can deny the claim without
recourse. Note: It is the responsibility f the
purchaser to file all necessary claims with the
carrier.
Notify the Traffic Department of all
damage within fifteen (15) days of shipment.
Storage
Equipment should be stored in its original
packaging in a clean, dry area. Store units in an
upright position at all times.
Unit Protection
Use shipping cartons, vinyl film, or an
alternative form of covering that can adequately
protect the unit on the job site. Open ends of
piping should always be capped. Avoid causing
physical damage to areas where painting,
plastering, and/or spraying has not been
completed. Take necessary precautions to avoid
contamination by foreign materials. Physical
damage and contamination may require the
equipment to be cleaned or other costly repairs
as this can prevent proper start-up.
Examine all pipes, fittings, and valves before
installing any of the system components.
Remove any dirt or trash found in or on these
components.
Pre-Installation
Installation, Operation and Maintenance
instructions are provided with each unit. Be sure
to completely read and understand these before
beginning installation. The installation site
chosen should include adequate service clearance
around the unit. Before unit start-up, read all
manuals and become familiar with the unit and is
operation. Check the system thoroughly before
operation.
Prepare the units for installation as follows:
1. Compare the electrical data on the unit
nameplate with the ordering and
shipping information to verify that the
correct unit has been shipped.
2. Keep the cabinet covered with the
shipping carton until the installation,
plastering, painting, etc. is complete.
3. Check the refrigerant tubing. Ensure it is
free of any dents or kinks, and verify
that it is not in contact with any other
parts in the unit.
4. Inspect all electrical connections.
Connections must be clean and tight at
the terminals.
5. Loosen compressor bolts on units
equipped with compressor spring
vibration isolation until the compressor
rides freely on the springs. Remove
shipping restraints.
*
NOTICE*
Failure to remove shipping
brackets (if installed) from spring-mounted
compressors will cause excessive noise, and
could cause failure due to added vibration.
CAUTION
Do not sore or install units in corrosive
environments or in locations subject to
temperature or humidity extremes (e.g.
attics, garages, rooftops, etc.). Such
conditions can significantly reduce
performance, reliability, and service life of
equipment.
CAUTION
Always move and store units in an upright
position. Tilting units on their sides may
cause equipment damage.
CAUTION
CUT HAZARD! Sheet metal parts may have
sharp edges or burrs. Use care and wear
appropriate protective clothing, safety
glasses, and gloves when handling parts
and servicing heat pumps.