Software Manual
5.4.4 Submenu I/O Settings
I/O Settings
J
Output 1
Cfg: None
JA
Output 1
Cfg: None
JAA
+
-
OK
Output 2
Cfg: None
JB
Set Output 2
Cfg: None
JBA
+
-
OK
Input
Cfg:None
JC
Set Input
Cfg: None
JCA
+
-
OK
Output 1 options:
•
None – No function
•
Error – Active if an error are detected
•
Run/Stop – Active if booster is running and not active when it is stopped.
•
Standby /off - active if booster is running or in standby.
Output 2 options:
•
None – No function
•
Delay start – Gives a signal at this port, before starting the pump.
The length of the delay is set in the settings menu, startup delay.
This function could for instance be used to secure start up of prepressure pump before starting the unit.
Input
•
None – No function
•
Release – unit unable to start before this signal is present.
•
Setpoint – Output pressure is controlled by external voltage source.
•
Chem. Low - Low level in chemistry can