Technical features and dimensions
2.3 - SMOKE
TURBULATORS
TRIMAX 3SC boilers are designed to be
used within an output range in order to
improve seasonal efficiency and coupling
with each heating system.
The heat output must therefore be
adjusted upon commissioning, based on
the guidelines of the Thermotechnical
Engineer, and always within the range
provided for each boiler on pages 9 - 13,
by the burner technician who will
determine the fuel flow rate.
In all cases,
make sure that the
turbulators are positioned inside their
respective smoke pipes.
While operating the boiler at minimum
output, the flue gas temperature must not
be lower than 160°C.
If not, make sure that all the turbulators
are inside the respective smoke pipes
before contacting our After-Sales Service.
The burner must be commissioned under
the responsibility of a qualified burner
technician authorised by the manufacturer.
On that occasion, a complete operating
report must be drafted.