9
420010355103
Max P15-25 / P15-25 AB
EN
6
1
2
3
4
5
SUNTEC
SUNTEC
P
V
SUNTEC ASV 47 A
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
2
1
4
5
6
P
-
+
V
P
3
7
DANFOSS BFP 21 R3
HYDRAULIC CIRCUIT
V2
V1
4
5
MAX P 15-25 :
The pump is a two pressure level type. During the test phase, it is adjusted to 10÷11 bar for
low flame, and 15÷16 bar for high flame.
PRIMING AND ADJUSTMENT OF OIL PUMP
8
6
5
4
3
2
1
7
SUNTEC
SUNTEC
P
V
SUNTEC AT3V 45A
9
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE
7 - PRESSURE ADJUSTMENT
8 - SPECIAL PRESSURE PORT
9 - CARTRIDGE FILTER
MAX P15AB
MAX P25AB
V2
V1
4
5
MAX P15-P25
V2
V1
4
5
1 - HOSE
2 - OIL FILTER
3 - OIL COCK
4 - SUCTION
5 - RETURN
1
1
2
3
3
6
5
4
3
2
1
7
SUNTEC
SUNTEC
SUNTEC
P
V
SUNTEC AT2V 45A+C
ADJUSTMENT DATA
NOZZLE : DANFOSS H÷S 80°÷60°; DELAVAN W 60°; STEINEN S 60°
NOZZLE
PUMP
OUTPUT
FIRING HEAD SETTING AIR DAMPER ADJUSTMENT
gph
spry
bar
kg/h
Pos.
Pos.
1,35
60°
15
6,28
0
1,5
1,50
60°
15
6,98
0,5
2,0
1,65
60°
15
7,68
1
2,3
1,75
60°
15
8,14
1,5
2,7
2,00
60°
15
9,3
2
3
2,25
60°
15
10,4
2,5
3,5
2,50
60°
15
11,64
3
4
2,75
60°
15
12,8
4
4,5
3,00
60°
15
13,9
5
5
1,75
60°
15
8,14
0
1,1
2,00
60°
15
9,3
1
1,5
2,25
60°
15
10,4
1,5
2
2,50
60°
15
11,64
1,8
2,2
2,75
60°
15
12,8
2
2,6
3,00
60°
15
13,9
2,2
3
3,50
60°
15
16,29
2,6
3,5
4,00
60°
15
18,6
3,1
3,5
4,50
60°
15
21,3
4
4,2
5,00
60°
15
24,2
5
5
5,50
60°
15
25,6
5
4,5
1,00+1,00
60°
12
8,3
0
1,1
1,10+1,10
60°
12
9,2
1
1,5
1,25+1,25
60°
12
10,4
1,5
2
1,50+1,50
60°
12
12,48
2
2,5
1,75+1,75
60°
12
14,6
2,5
3
2,00+2,00
60°
12
16,65
3
3,5
2,25+2,25
60°
12
18,73
3,5
3,8
2,50+2,50
60°
12
20,8
4
4
2,75+2,75
60°
12
22,9
4,5
4,5
3,00+3,00
60°
12
25
4,5
5
MAX P15 - P15 AB
MAX P25 AB
MAX P25