background image

13

www.ecoflam-burners.com

EN

420010813300

INSTALLATION

Electrical connections

!

WARNING:

Electrical wiring must be carried out with electrical supply disconnected and with burner switch in position OFF.

Electrical supply must correspond to the one shown on the burner label.

APPLICABLE STANDARD

The electrical connection work comprising
all the installation materials, terminals and
earth connections must be carried out in
accordance with the applicable
regulations. For the electrical installation of
the burner care must be taken to observe
the circuit diagram made out for the
furnace system.
The electrical connection of the burner and
instruments shall be entrusted to
authorized specialists only.

NOTE:

For the installation of the

connection cables care must be taken to
provide cable loops of sufficient length to
allow for the swing-out of the boiler door
and burner. 
Make sure after the completion of the
electrical connection work to check the
wiring of the electrical system of the
burner. This should include a check of the
direction of rotation of the burner motor
(fan).

GENERAL WARNINGS:

All applicable electrical safety regulations
must be followed. Failure to correctly
dimension the suitable input power and
earth the equipment  may cause damages
to person and compromise the correct
function of the burner therefore the
electrical system shall be checked by
qualifed personnel. 
The manufacturer declines all
responsibility for modifcations or
connections different from those shown in
the electrical scheme.
Adapters, multiple plugs and extension
cables may not be used for the
equipment’s power supply. 
An omnipolar switch in accordance with
current safety regulations is required for
the mains supply connection.

ELECTRICAL CONNECTION
1) of the burner

- Built-in electrical cabinet
Use cable gland in order to secure the
required level of protection. All the links,
power and control, are connected to the
terminal block of the cabinet. Provide
cables in sufficient length to secure the
rotation of the burner body according to
the assembly.
Check and adjust the size of the
contactors and thermal relays and the
wires section according to the motor and
supply voltage specs.

ATTENTION:

Wiring is not supplied.

The burners are produced with
connections suitable for power supply
380-400 V three-phase.

The burners with electric motors of an
output lower or equal to 3 kW can be
adapted to 220-230 V (please follow the
instructions on the backside); motors with
higher output can only work 380-400 V
three-phase. In case of request of burners
different from the above mentioned
standard, it is recommended to make
specific mention in the order.

Instructions: how to adapt electric
motors of an output lower or equal to 3
kW to 220-230 V  power supply

It is possible to change the voltage of the
burner by operating as follows:
1. change the connection inside the
electric box of the motor, from star to delta
(see picture 1);
2. change the setting of the thermal relay,
referring to the absorption values   indicated
in the motor nameplate. If necessary,
replace the thermal relay with another one
of suitable scale.This operation is not
possible on motors above 3 kW.
For more information, please contact the
Ecoflam staff.

LEGENDA

HLB: lock-out lamp
STAB: two stages thermostat
HLF: burner on flame lamp
STC: boiler thermostat
STS: safety thermostat
SA: active probe
SP: passive probe

T

P

P

T

P

T

STAB

9

Q

N

R

S

T

7

6

5

8

S

N

T

R

PE

50 Hz 400V

13

12

11

10

4

1

2

3

STC

HLB

STS

HLF

PROBES CONNECTION

9

13

12

11

10

SA

Q

BE

....

G

L

M

U1

ACTIVE PROBE CONNECTION

(FOR MODULATING VERSION)

12

13

11

9

10

S

P

Q

AE

...

M

B

PASSIVE PROBE CONNECTION

(FOR MODULATING VERSION)

230V

400V

fig.1

Summary of Contents for MAIOR P 500-1 PRE

Page 1: ...P 500 PRE 1 TC MAIOR P 500 PRE 1 TL S 3144806 Technical data Operating instructions Electric diagrams Spare parts list MAIOR P 500 1 PRE MAIOR P 600 1 PRE www ecoflam burners com LIGHT OIL BURNERS 10...

Page 2: ...for light oil 12 Electrical connections 13 Start up checking procedure 14 Exhaust gas test 15 Start up oil side 16 Fuel selection Start up 16 Adjusting the max air flow rate 16 Firing head setting 16...

Page 3: ...to grant correct working of the burner Installation start up and maintenance must be carried out by authorised specialists and all applicable guidelines and regulations including local safety regulati...

Page 4: ...DIESEL Biodiesel KEROSENE Kerosene FUEL 420010813300 EN www ecoflam burners com 4 230 400 50 230 400 Volt 50 Hz ELECTRICAL POWER SUPPLY MODULAR DELIVERY SYSTEM Light oil burners All light oil burners...

Page 5: ...BURNER DESCRIPTION 420010813300 EN www ecoflam burners com 5 Control panel SAL main switch I 0 HLF working lamp HLBT thermal lock out lamp V R HLF HLBT 1 ON 0 OFF 0 I SAL...

Page 6: ...s std Standard Class 1 OIL EN267 250 mg kWh Control unit Type LAMTEC ETAMATIC BT3xx Air regulation Type Air flap Air flap Air flap control with servomotor Model LAMTEC Flame monitoring Type UV CELL Ig...

Page 7: ...8000 kW L flame m 5 m medium value D flame m 1 m medium value WARNING Some flame modifications can be done in our FLEXSHOP in the factory in order to shape the flame and adapt it to some special boil...

Page 8: ...570 965 330 330 M16 Fixing hole dimensions are I and L as per dimension table Boiler hole shall be done according to the blast tube dimension F plus 15 25 mm in order to be able to extract it during...

Page 9: ...ner will sweep the furnace compartment and exhaust ports at the required air flow rates At the end of the specified pre ventilation time the air damper will be moved into its partial load position Thi...

Page 10: ...conical angle of 60 Gap 6 must be filled with an elastic non combustible insulation material For boilers with reverse firing the minimum burner tube insertion depth A as specified in the boiler manuf...

Page 11: ...THE PRESSURE OIL SUCTION PRESSURE The maximum permissible vacuum is 0 4 bar At higher vacuum levels the fuel oil will tend to separate air from oil which may lead to operating trouble In the ring line...

Page 12: ...eplaced NOZZLE CHART IS AVAILABLE ON APPENDIX PAGE Oil under suction Oil under pressure Pressure gauge port To nozzle Pressure adjustment By pass plug inserted By pass plug removed Return Intake from...

Page 13: ...n ELECTRICAL CONNECTION 1 of the burner Built in electrical cabinet Use cable gland in order to secure the required level of protection All the links power and control are connected to the terminal bl...

Page 14: ...the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results OIL START UP Open all shut off valves of oil supply system Set fuel selector switc...

Page 15: ...2max WARNING if the installation is above sea level the output of the burner vary base on the diagram The regulation of the burner in this case shall take into account the reduced power of the burner...

Page 16: ...ease burner output from the low ame to the high ame and set oil servomotor curve in order to have a stable ame Refer to LAMTEC manual attacched Firing head setting The firing head is pre adjusted at t...

Page 17: ...priming Start the burner and check the pump feeding pressure In case the pump priming does not take place during the first pre purging with a consequent subsequent lock out of the burner rearm the bur...

Page 18: ...mp VS Oil safety valve 3 Adjusting cam 4 Check valve VL Working valve PR Pressostat optional 5 Nozzle 6 Pressure regulator 7 Manometer pressure gauge Adjusting the intermediate burner capacity Oil adj...

Page 19: ...lly and check the tightening of the O rings replace them if necessary Make visual inspection of the burner s electrical components and eliminate malfunctions if necessary Burner safety devices functio...

Page 20: ...f the electrodes after any intervention as wrong position could cause ignition troubles REMOVING THE BLAST TUBE REMOVING THE FIRING HEAD POSITION OF ELECTRODES 420010813300 EN www ecoflam burners com...

Page 21: ...the control box and watching the start up and operating program APPENDIX Function Lamtec BT3xx control and safety unit Refer to LAMTEC manual attacched Pressing the unlocking button on the unit for c...

Page 22: ...rying the return pressure while keeping the supply pressure at a constant level Prior to burner start check the nozzle size against the required output It might be necessary to replace the nozzle see...

Page 23: ...0 175 B 20 285 280 275 270 270 265 265 260 255 250 245 240 230 200 185 170 150 175 A 25 60 61 62 63 64 65 66 68 70 72 78 80 82 85 92 98 105 110 120 140 160 175 B 25 330 330 330 330 325 325 325 320 315...

Page 24: ...5 155 170 190 215 240 275 350 B 20 590 580 570 560 550 540 530 500 480 465 450 440 400 375 360 340 350 A 25 120 122 124 126 128 132 134 136 138 140 145 150 155 165 175 185 200 225 255 275 350 350 B 25...

Page 25: ...210 230 250 275 300 340 410 475 B 20 740 735 730 720 710 700 680 660 640 620 490 560 530 500 475 450 475 A 25 140 162 164 166 168 170 175 180 188 195 205 215 225 245 265 280 305 340 380 480 475 B 25...

Page 26: ...ALLATION Return plugged Inlet end return G 1 2 To nozzle G 1 2 Pressure gauge port G 1 4 Vacuum gauge port G 1 4 40 20 30 35 10 15 25 5 1000 1200 1400 200 400 0 600 800 TA5 TA4 TA3 TA2 0 900 1500 1100...

Page 27: ...15 2 KMP R S T NO FMP 3 M MV U V W USCITA 4 20mA PER MONITORAGGIO POTENZA BRUCIATORE OUTPUT 4 20mA FOR BURNER POWER MONITOR INGRESSO 0 4 20mA PER REGOLATORE DI POTENZA DEL BRUCIATORE INPUT 0 4 20mA FO...

Page 28: ...VENTILATORE KMV FMV RELE TERMICO MOTORE VENTILATORE REMOTE CONTROL SWITCH FAN MOTOR CONTACTEUR MOTEUR VENTILATEUR TELERRUPTOR MOTOR VENTILATOR MOTOR THERMAL RELAY FAN MOTOR RELAIS THERMIQUE MOTEUR VE...

Page 29: ...om EN 420010813300 APPENDIX Spare parts MAIOR P 500 1 PRE MAIOR P 600 1 PRE 44 3 2 10 13 21 7 38 19 37 32 20 35 33 36 34 28 29 3 2 45 31 12 16 15 43 42 17 14 1 0 23 11 24 25 BT3xx L C M 1 0 0 18 8 9 6...

Page 30: ...46 TLX 740170016500 20 ELECTRODES 65325903 65325903 21 IGNITION TRANSFORMER Brahma T8 13000 35 65323222 65323222 22 SELECTOR 23 MAIN SELECTOR ART ECX1040 65325032 65325032 24 FUSE SUPPORT HK 520 04 1...

Page 31: ...31 www ecoflam burners com EN 420010813300...

Page 32: ...ul to its products without affecting their main features Ecoflam Bruciatori S p A si riserva il diritto di apportare ai prodotti le modifiche che riterr necessarie o utili senza pregiudicarne le carat...

Reviews: