18
420010300700
Maior P 700.1 / 1200.1 PR
EN
SUNTEC TA.......
PRIMING AND ADJUSTMENT OF OIL PUMP
VERIFY:
- That piping system is perfectly sealed;
- That the use of hoses is avoided whenever is possible (use copper pipes preferably);
- That depression is not greater than 0,45 bar, to avoid pump’s cavitation;
- That check valve is suitably designed for the duty;
The pump pressure is set at a value of 22-25 bar during the testing of burners. Before starting the burner, bleed the air
in the pump through the gauge port. Fill the piping with light-oil to facilitate the pump priming. Start the burner and
check the pump feeding pressure. In case the pump priming does not take place during the first prepurging, with a con-
sequent, subsequent lock-out of the burner, rearm the burner’s lock-out to restart, by pushing the button on the control
box. If, after a successful pump priming, the burner locks-out after the prepurging, due to a fuel pressure drop in the
pump, rearm the burner’s lock-out to restart the burner. Do never allow the pump working without oil for more than
three minutes. Note: before starting the burner, check that the return pipe is open. An eventual obstruction could dama-
ge the pump sealing device.
1
2
6
3
4
1
4
3
6
5
2
SUNTEC T.......
4 - VACUUM GAUGE PORT
5 - REGULATING VALVE TV
6 - TO NOZZLE
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
6
1) Remove the cap A of the pres-
sure regulating valve TV.
2) Loosen the fixing nut B and
use an allen wrench on the screw
C to adjust the delivery oil pres-
sure. To increase the pressure turn
clockwise, to decrease the pressu-
re turn anticlockwise.
3) Tighten the nut B and pay
attention not to turn also the
adjusting screw.
4) Screw on the cap A, back to its
previous position.
PRESSURE REGULATING VALVE ADJUSTMENT
A
B
C
B
A
1
2
3
4
Summary of Contents for MAIOR P 1000.1
Page 5: ...5 420010300700 Maior P 700 1 1200 1 PR IT...
Page 6: ...6 420010300700 Maior P 700 1 1200 1 PR IT...
Page 8: ...8 420010300700 Maior P 700 1 1200 1 PR IT...
Page 19: ...19 420010300700 Maior P 700 1 1200 1 PR EN 0 0 1 0 1 0 2 3 4 0 0 5 6 6 7 6 0 88 9...
Page 21: ...21 420010300700 Maior P 700 1 1200 1 PR EN...
Page 22: ...22 420010300700 Maior P 700 1 1200 1 PR EN...
Page 34: ...34 420010300700 Maior P 700 1 1200 1 PR FR...
Page 63: ...63 420010300700 Maior P 700 1 1200 1 PR RU...
Page 71: ...71 420010300700 Maior P 700 1 1200 1 PR RU 0 2...
Page 78: ...78 420010300700 Maior P 700 1 1200 1 PR IT EN FR ES RU...
Page 79: ...79 420010300700 Maior P 700 1 1200 1 PR IT EN FR ES RU...