Ecoflam BLU TS 3000.1 PR HT Manual Download Page 12

12

www.ecoflam-burners.com

EN

420010487501

INSTALLATION

Gas line

GAS CONNECTION PRESSURE

A minimum connection pressure must be
available upstream of the burner gas valve
to ensure the proper functioning of the
burner.

WARNING:

the total gas pressure loss

must always be smaller than the available
gas flow pressure.

For the installation of the valves and
instruments group take care to observe the
mounting instructions supplied by their
manufacturers (these are packed with the
equipment).
The gas line installed to the burner must
be dimensioned in accordance with the
throughput rate and the available
pressure.
For selecting the nominal bore “DN” of the
gas valves and instruments group care
should be taken to observe the flue
resistance of the boiler and the gas
pressure loss of the burner and valves and
instruments group.

GAS VALVES AND INSTRUMENTS GROUP

The gas valves and instruments group can
be connected directly to the gas feed line.

Take care to observe the correct order of
installation and direction of flow (arrow on
housing).
Check the valves and instruments and
connection pieces for absence of dirt
particles and foreign matter before
installation and initial operation. To provide
effective conditions for start-up make sure
the distance between the burner and the
gas stop valve is as short as possible.

LEAK TEST

The gas line upstream of the burner gas
valves and instruments group must be
installed in accordance with the applicable
regulations, checked for absence of leaks,
vented and certified accordingly by the gas
installation company. The screwed unions
and flanged joints must be checked for
proper tightness (by making a pressure
test). The leak test must be made under
pressure using approved foaming agents
which do not cause corrosion. For steam
boiler furnaces the result of the leak test
must be duly certified.

VENTING

Prior to taking the burner into operation or
after any repair work make sure to vent the
complete gas feed line and the gas valves
and instruments group into the open
atmosphere (e.g. by means of a hose)
taking care to avoid any hazards.
In no case should the gas line be vented
into the heating or furnace chambers.
Make use of a test burner to check the 
gas-carrying spaces are free from an
inflammable gas mixture.

SUPPORT

The valves and instruments group must be
supported with a telescopic jacking
member or similar during and after
installation (e.g. on filter and valve).

JOINT

It is recommended to provide an easy to
disconnect joint (with planar sealing faces)
to facilitate repair work on the boiler
(furnace) and allow the boiler door to be
swivelled out if required.

M

Air

Gas

313

160

142

141

120

150

314

349

151

100

143

To be supplied by the installer

To be supplied by the installer

100 Burner
120 Air 

damper

141 Ball 

valve

142 Gas 

filter

143 Antivibration 

coupling

144 Gas 

governor

150 Throttle 

valve

151  Gas train Siemens VGD.... 
160 

Kit 

tightness control (optional)

313  Min.gas pressure switch 
314  Max.gas pressure switch (optional)
349  Air/gas damper motor

 

144

GAS VALVES AND INSTRUMENTS GROUP

The gas valves and instruments group used
with the furnace will be selected according to
the specific requirements to be met by a
burner system.
The following factors must be taken into
account:
• burner output
• furnace back pressure
• gas pressure loss of the burner head
• gas pressure losses of the gas valves and
instruments group

NOTE: 

Only gas trains assembled by the burner manufacturer and approved in

accordance with the burner test specifications.
EN676 compulsory kit and accessories in order to comply to the safety regulations. 
Additional accessories and kits shall be installed by the installer in accordance to the
local safety regulations and codes of practise.

CONNECTION DIAGRAM FOR BURNERS WITH 
GAS TRAIN SIEMENS VGD...

Summary of Contents for BLU TS 3000.1 PR HT

Page 1: ...GAS BURNERS EN BLU TS 3000 1 PR HT BLU TS 4000 1 PR HT Gas train manual is separate www ecoflam burners com BLU TS 3000 1 PR TC SGT HT 230 50 3143084 BLU TS 3000 1 PR TL SGT HT 230 50 BLU TS 4000 1 P...

Page 2: ...Head loss diagram 13 Pressure loss diagrams 14 Electrical connections 16 Start up checking procedure 17 Exhaust gas test 18 Start up 19 Adjusting the max air flow rate 19 Firing head setting 19 Servo...

Page 3: ...ral EN676 directives and guidelines must be observed EN676 compulsory kit and accessories in order to comply to the safety regulations Additional accessories and kits shall be installed by the install...

Page 4: ...gulations For burners over 1700 kW gas train connection pipe must be ordered Kits and accessories are managed and delivered separately Component type BBCH Burner Body with Combustion Head without gas...

Page 5: ...ixing flange 9 Air flap regulation 12 Lifting eyebolts 13 Mechanical cam gas 15 Servomotor for gas and air 16 Gas train 19 Gas filter 20 Ball valve 23 Antivibration coupling 24 Tightness control GTCP...

Page 6: ...TRAIN INTO THE BURNER AND CALCULATE THE OVERALL DIMENSIONS refer to the dimension page and thE gas train manual for all detailed information Gas governor Filter FGDR FILTER Compulsory EN676 Tightness...

Page 7: ...kcal Nm3 G30 L C V 29 320 kcal Nm3 Emission class std Standard Class 2 GAS EN676 120 mg kWh Control unit Type LFL LGK Gas train GT VGD separate gas train Filter KIT Tightness control Other KIT ACS Gas...

Page 8: ...the boiler backpressure Example Burner thermal output 8000 kW L flame m 5 m medium value D flame m 1 m medium value WARNING Some flame modifications can be done in our FLEXSHOP in the factory in orde...

Page 9: ...der to be able to extract it during maintenance Burner boiler mounting flange Packaging only burner WARNING Please follow the suggested dimension for the hole on the boiler flange in order to fit the...

Page 10: ...m will vary the positions of the gas control valve and air damper and thus regulate the gas flow rate in a linked concept with the air flow rate The burner can either be controlled by a 2 stage slidin...

Page 11: ...be and the boiler lining must be sealed with appropriate insulating material BURNER LINING Check before burner installation 1 Depending on the type of boiler reverse flame or three pass check the burn...

Page 12: ...es the result of the leak test must be duly certified VENTING Prior to taking the burner into operation or after any repair work make sure to vent the complete gas feed line and the gas valves and ins...

Page 13: ...ording to the instructions of the gas train separate manual KITPRES Maximum pressure switch assembly Maximum pressure switch is provided as a kit and shall be assembled into the main gas train accordi...

Page 14: ...LU 3000 1 PR MULTICALOR 300 1 MULTIFLAM 300 1 VGD 40 100 no neutral 20 700 1C FILTER DN 100 22 700 VGD 40 080 no neutral 30 700 FILTER DN 80 35 700 VGD 40 065 no neutral 45 700 FILTER DN 65 55 700 VGD...

Page 15: ...Inlet gas pressure MIN mbar Inlet gas pressure MAX mbar Diagram BLU 4000 1 PR MULTICALOR 400 1 MULTIFLAM 400 1 VGD 40 100 no neutral 27 700 2C FILTER DN 100 30 700 VGD 40 080 no neutral 40 700 FILTER...

Page 16: ...be checked by qualifed personnel The manufacturer declines all responsibility for modifcations or connections different from those shown in the electrical scheme Adapters multiple plugs and extension...

Page 17: ...be available the exhaust gas duct up to the measuring point must be free of leaks to prevent anomalies in the measurement results GAS START UP Connect the measuring instruments for the gas head pressu...

Page 18: ...to be exceeded DETERMINING THE VOLUMETRIC GAS FLOW RATE The thermal furnace output of a boiler QF is the amount of heat supplied with the gas in a unit of time When taking the burner into operation t...

Page 19: ...ut the adjusting Firing head setting Servomotor SQM50 Air damper motor pre setting The cams of the servomotor are set from the factory in order to start the burner and reach the maximum output The fol...

Page 20: ...the adjustment value of the air pressure switch until to have the burner lockout Remove the obstruction from the air intake screw on the cover C and start the burner by pressing the control box rearm...

Page 21: ...with air periodically replace it if necessary After the cleaning of the components of the gas train perform the leakage test Make visual inspection of the burner s electrical components and eliminate...

Page 22: ...duction in the ionization current and cause a safety shut off of the burner due to a flame detection failure In this case check the position of the electrode its electric connection and the earthing o...

Page 23: ...age controller if necessary X YES Leakage Test failure LDU kit Check contacts clean valves or replace leakage controller if necessary X YES SEQUENCE START Servomotor OPEN position switch not reach Che...

Page 24: ...not closed between terminals 12 and 4 or 4 and 5 or the contacts of all control and safety units in the controlled system are not closed e g gas pressure or air pressure switches temperature or pressu...

Page 25: ...he reversible actuator is fitted with a synchronous motor which drives a shaft via a gearbox The shaft end carries a coupling to drive the fuel and combustion air controlling element The SQM actuator...

Page 26: ...FICATION DESCRIPTION ECN MODIFICATION BLU TS 3000 1 4000 1 5000 1 6000 1 PR SGT QUADRO COMANDI A POZZOBON 28 03 2012 2 420110081300 1 A RIGONI LANDIS SQM 50 481A2 ER RBA12CB103 LANDIS LFL 1 333 1 622...

Page 27: ...E TERMICO MOTORE VENTILATORE FUSIBILE FILTRO ANTIDISTURBO INTERRUTTORE GENERALE CON FUSIBILE KMV HLB FMV FU FUSE Z Q ESPIA DE FUNCIONAMIENTO LAMPE DE FONCTIONNEMENT LAMPADA DI FUNZIONAMENTO HLF WORKIN...

Page 28: ...DI TENUTA YVGS YVG F 1 E D 2 3 4 C B A 1 2 3 4 5 6 7 8 F E D 5 6 7 C B 8 A 2 1 3 TOT SHEET SHEET DESIGNER DESCRIPTION DATE FIST CREATION CODE SIGNATURE R D DEPARTMENT CONTROLLER Ecoflam Bruciatori SE...

Page 29: ...ELETTROVALVOLA GAS SPGmin YVGS YVG YVG YVGS T P SPGmin T P SPGmin YVGS YVG NON UTILIZZATA VI CAMMA DI REGOLAZIONE ARIA BASSA FIAMMA LAVORO CAMMA REGOLAZIONE ARIA ACCENSIONE MINIMA POTENZA CAMMA REGOL...

Page 30: ...APPENDIX Spare parts list 420010487501 EN www ecoflam burners com 30 19 23 24 2 Blu TS 3000 1 4000 1 PR 1 20 3 4 8 7 10 9 16 11 13 14 15 17 12 21 5 6 22 25 18 26...

Page 31: ...ELECTRODE 65320891 65320891 10 IONIZATION PROBE 65320892 65320892 11 GAS PIPE TC 65321664 65321664 TL 12 ROD TC 65320242 65320242 TL 65320243 65320243 13 FIRING HEAD 65321666 65321666 14 DISC 65320742...

Page 32: ...ul to its products without affecting their main features Ecoflam Bruciatori S p A si riserva il diritto di apportare ai prodotti le modifiche che riterr necessarie o utili senza pregiudicarne le carat...

Reviews: