![Ecoflam BLU 1000 P AB Manual Download Page 13](http://html1.mh-extra.com/html/ecoflam/blu-1000-p-ab/blu-1000-p-ab_manual_2354230013.webp)
pag.13
LB 448
Blu 500 ÷ 1400 P AB
B
POSITION OF ELECTRODES
SHIFTING FROM NAT. GAS TO L.P.G.: Remove the front disk from the firing head and fit the rear disk.
SHIFTING FROM L.P.G. TO NAT. GAS: Remove the rear disk from the firing head and fit the front disk.
POSITIONING THE DISK FOR NATURAL GAS AND L.P.G.
2 Ö 3 mm
2 Ö 3 mm
BLU 500-700-1000 PAB
BLU 1200-1400 PAB
Ignition electrode
Ionization probe
Ignition electrode
Ionization probe
I
0
REMOVING THE NOSEPIECE
In order to change the burner operation from natural gas to LPG you have to
follow these instructions (as shown in figure).
- remove the disc from combustion head. - carry out the thread M6 on the 3
holes Ø 5. - put on each threaded hole a screws M6.
- replace the disc on the combustion head.
M6
HOW TO CHANGE BURNER OPERATION FROM
NATURAL GAS TO LPG - BLU 500
ONLY BLU 700-1000 PAB
SHIFTING FROM NAT. GAS TO L.P.G.: Remove the front disk from the firing head
SHIFTING FROM L.P.G. TO NAT. GAS: Fit the front disk to the firing head
Open
Clo
s
ed
NATURAL GA
S
L.P.G.
Blu 1200