03.03.2021 Rev. 01
24
12.
EMISSION SETTINGS
Check the emission values at minimum and maximum capacities again and adjust combustion parameters
precisely by following above steps.
After adjustment of parameters are finished, close all measurement points as they will be leak proof.
Flue gas emission values and flue gas temperature limit values are given at below table:
O2
<5,5
%
CO
<50
ppm
CO2
8,4-9
%
Flue Gas
Temperature
<80
°C
Summary of Contents for WT-S 35
Page 10: ...03 03 2021 Rev 01 9 4 PARTS...
Page 11: ...03 03 2021 Rev 01 10 5 BOILER HYDRAULIC SCHEMA...
Page 14: ...03 03 2021 Rev 01 13...
Page 20: ...03 03 2021 Rev 01 19 10 ELECTRICAL DIAGRAM AND RELATED CONNECTIONS...
Page 22: ...03 03 2021 Rev 01 21...
Page 23: ...03 03 2021 Rev 01 22...