8
Rear Brick
Pull the top edge of the Rear Brick forward and lift
the brick out of the Stove.
Baffle / Throat Plate
Lift the Baffle and slide to the left. When the right
side of the Baffle clears the Baffle Support, lower
the Baffle into the Fire Box and remove.
To assemble the stove, simply reverse the above
procedure.
PRE-INSTALLATION
REQUIREMENTS
W
ARNING
!
You run the risk of serious health problems if the
products of combustion enter the property.
P
LEASE CHECK THE FOLLOWING
:
Any existing chimney/flue system must be
confirmed as suitable for this appliance as defined
in Building Regulations Document J. It must be
swept and inspected, by a competent person (see
notes), to confirm that is structurally sound and free
from cracks and obstructions. The diameter of the
Flue should not be less than Ø127mm and not more
than Ø200mm. Do not connect to systems that have
large voids or spaces. If any of these requirements
are not met, the chimney should be lined by a
suitable method.
If the chimney is suspected of previously serving an
open fire it must be swept again, within a month of
regular use, to clear any soot that may have been
dislodged due to the variation in combustion levels
and higher flue gas temperature levels. The
chimney/flue system exit must comply with Building
Regulations Document J. The minimum height of
the chimney/flue system must be 4.5 metres from
the hearth to the top exit. There must be no
horizontal sections and must not have more than 4
bends. These bends must have angles of 45° or less.
Make provision to remove the appliance without
affecting the chimney/flue system. Make provision
to access the chimney/flue system for cleaning and
the removal of debris. If there is no existing
chimney then either a prefabricated block chimney
in accordance with Building Regulations Approved
Document J, or a twin-walled insulated stainless
steel flue to BS4543 can be used. These chimneys
must be fitted in accordance with the
manufacturer’s instructions and Building
Regulations. New masonry and flue block chimneys
must meet the requirements of Building
Regulations Document J. Any connecting flue pipe
systems must also meet these regulations.
Summary of Contents for eco 4
Page 22: ...22 Body Assembly Spares...