Without room unit, thermostat or outside temperature control, constant flow temperatures
without a mixing or secondary circuit.
Function No.
Room Temp Control
Max Flow Temperature
30 None
55
°
C
31 None
70
°
C
32 None
85
°
C
Without room unit, thermostat or outside temperature control, constant flow temperatures with a
mixing or secondary circuit.
Function No.
Room Temp Control
Max Flow Temperature
33 None
70
°
C primary
34 None
85
°
C primary
eco hometec cascade manager KKM2 Settings (for controlling up to nine boilers)
Function No.
Cascade manager
Max Flow Temperature
35
KKM2
CH temp on KKM2
Analogue cascade manager with signal 0…3 Volts.
Function No.
Cascade manager
Max Flow Temperature
36
Analogue 0…3 Volts
CH temp on manager
The following function numbers are valid when a
pump
is used to load the hot water cylinder
Outside temperature controlled without mixing circuit
Function No.
Room Temp Control
Max Flow Temperature
37 RE
2132 55
°
C
38 RE
2132 70
°
C
39 RE
2132 85
°
C
40 240v
Room
Stat
55
°
C
41 240v
Room
Stat
70
°
C
42 240v
Room
Stat
85
°
C
TRV’s
55
°
C
44 TRV’s
70
°
C
45 TRV’s
85
°
C
43
Outside temperature controlled with mixing circuit
Function No.
Room Temp Control
Max Flow Temperature
46
With two RE 2132
70
°
C primary
47
With two RE 2132
85
°
C primary
48
With one RE 2132
70
°
C primary
49
With one RE 2132
85
°
C primary
50 240v
Room
Stat
70
°
C primary
51 240v
Room
Stat
85
°
C primary
52 TRV’s
70
°
C primary
53 TRV’s
85
°
C primary
Page 44