At 60 Hz frequency, running times and torques are about 17% less.
Parameter
Description
Operating Voltage
AC 120 V -15% / +10%
AC 230 V -15% / +10%
Operating Frequency
50 to 60 Hz ±6%
Power Consumption
10 VA
Duty Cycle, ED
100%
Operating Angle
Adjustable between 0 and maximum 90° (scale range)
Mounting Position
Multi-position
Degree of Protection
IP66 / NEMA 4
Cable Entry
2 x M16 without thread or 2 x 1/2" NPT thread
Direction of Rotation
Facing the shaft end:
clockwise or counterclockwise, dependent on model
Torque
10 Nm, depending on the type
1
(Holding torque is 5 Nm)
Running Time, 90° stroke
30 seconds depending on the type
1
Drive Motor
Synchronous motor, stall protected
Gear Train
Maintenance free gears and bearings
End and Auxiliary Switches
Type
To DIN 41636
Switching Voltage
AC 24 to 250 V
Switching Capacity
1A, 250 VAC
7A, 250 VAC Peak load < 0.5 seconds
Number of End Switches
2
Number of Auxiliary Switches
Maximum of 4
Drive Shaft
Factory supplied, not replaceable
Operating Temperature
-
20 to +60 °C (0 to 140 °F)
Storage Temperature
-
40 to +70 °C (-40 to 158 °F)
Humidity
<
95% RH noncondensing
Weight
Approximately 2 kg
Materials of Construction
Housing
Die Cast Aluminum
Cover
Impact-proof and heat resistant plastic
Specifications