4

2.0 Burner Operation and Controls

Failure to use suitable flame sensing devices and automatic fuel shut-off
valves can cause explosions and fires. The owner/user and/or his insur-
ance underwriter is responsible for providing, using, and maintaining
suitable limit controls, flame supervision, and other safety devices for this
burner, and for properly interfacing all electrical equipment and sequenc-
ing burner operation.

Turndown Method

Ratiomatic burners are designed to operate with either two-position or modulating
temperature control systems. Gas-air ratio control is performed by a ratio regulator
as shown in Figure 2.

Control Motor Requirements

Stroke:

  90

°

. For applications with unusually high backpressures or drafts, motor

travel may need to be restricted to less than 90

°

. Eclipse recommends adjustable

stroke motors or motors with travel-limiting auxiliary switches for these jobs.

Timing:

  15 seconds minimum.

Mounting:

  Can be mounted on either side of the burner. However, if an air inlet filter

is used, the control motor must be mounted on the side opposite the filter.

Piloting

A spark ignited pilot is an integral part of each burner. An adjustment cock is included
for pilot adjustment.

The customer must provide a pilot gas valve train that includes a pilot gas regulator
and a solenoid valve.

If combustion chamber pressure is likely to be more than 

±

 1"w.c. (2.5 mbars) or if

it is expected to fluctuate during operation, cross-connect the pilot regulator vent to
the chamber.

Flame Monitoring

50 thru 600 sizes:

 A flame rod is included with the burner; UV scanners and mount-

ing kits are available as options.

750 thru 2500 sizes:

 UV scanner only; must be ordered separately.

Main Gas Valve Train

Gas should be supplied to the burner inlet through a valve train which complies with
NFPA Standards and all applicable local codes.

When multiple burners are fed from the same valve train, a check valve must be in-
stalled in the gas line as close as possible to the proportionator inlet to prevent un-
even flows at low fire. Main regulator pressure may need to be increased to com-
pensate for the check valve pressure drop.

CAUTION:  Customer supplied main gas regulators for inlet pressures greater
than 1 psig (70 mbars) for 50-200 Ratiomatics or 5 psig (350 mbars) for 300-
2500 Ratiomatics must be capable of tight shut-off to prevent leakage and sub-
sequent proportionator damage.

Limit Controls

Limit controls and safety equipment should comply with current NFPA Standard 86
and all applicable local codes and/or standards. NFPA Standards are available from:

National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts  02269

Blower Shut-Off

During shutdown, the blower must not be turned off until the chamber temperature
has dropped below 250

°

 F (121

°

 C). This is to prevent hot gases from flowing back

through the burner and blower and damaging them.

WARNING

13

5.0 Trouble-shooting

Trouble-shooting of panels and electrical circuits should be done by quali-
fied plant electricians, technicians, or engineers experienced in all facets
of this type of combustion equipment.

CAUTION

CAUSE(S)

PROBLEM

Burner behaves erratically, does
not respond to adjustment.

Main flame too long & yellow at
high fire.

Main flame too short at high fire.

Low fire (pilot) flame is long,
soft or yellow.

Low fire flame is weak or
unstable.

Main flame fails to light or goes
out as burner cycles to high fire.

Pilot fails to light.

1. On initial start-up, gas line may be filled with air. Repeat ignition

trial several times to purge.

2. No power to ignition transformer or pilot solenoid.

3. Open circuit between ignition transformer and spark plug.

4. Spark plug needs cleaning.

5. Spark plug center electrode grounded against burner.

6. Spark plug improperly grounded. Do not use pipe dope on ignition plug

threads.

7. Pilot gas cock screw closed.

8. Insufficient gas pressure into or out of pilot regulator.

1. Pilot set too lean, becoming unstable as air increases.

2. Insufficient pressure into or out of main gas regulator.

3. Main gas adjusting valve not open enough.

4. Marginal air pressure switch setting.

5. Suction or backpressure in chamber fluctuates, upsetting pilot stability.

Cross-connect pilot regulator vent to the combustion chamber, but not via
the burner air pressure tap.

1. Gas flow is insufficient. Open pilot gas cock adjusting screw or increase

pressure out of pilot gas regulator.

1. Burner internals loose, dirty or burned out. If any of these problems exist, con-

tact your Eclipse representative or the Eclipse factory for service.

1. Gas flow is too high. Gas butterfly valve is open too far, or main gas regu-

lator spring is screwed in too far.

1. Gas flow is too low. Gas butterfly valve is closed too far, or main gas regu-

lator spring is screwed out too far.

1. Too much gas flow. Main gas proportionator spring is set for too much

flow, or pilot gas cock adjustment is open too far.

2. Insufficient air flow due to dirty blower filter or impeller.

Summary of Contents for RatioMatic 50

Page 1: ...e attempting to light burners If you do not understand any part of the information in this Guide contact your local Eclipse representative or Eclipse Combustion Inc before proceeding further Important...

Page 2: ...t See Figure 6 for filter element replacement Spark Plug Flame Rod Replacement Ignition plugs and flame rods wear out over long periods of normal burner opera tion For Ratiomatic burners the part numb...

Page 3: ...4 9 6 1 7 3 7 5 4 5 7 4 8 1 9 8 12 0 9 1 8 7 12 3 3 0 3 9 4 4 4 0 4 5 6 4 7 2 4 5 6 5 7 0 8 5 10 7 8 1 7 9 11 4 1 0 2 8 3 4 3 0 3 5 5 4 6 1 4 0 5 8 5 9 6 9 9 4 7 0 7 0 10 5 0 0 2 3 2 8 2 5 2 9 4 9 5 5...

Page 4: ...portionator damage Limit Controls Limit controls and safety equipment should comply with current NFPA Standard 86 and all applicable local codes and or standards NFPA Standards are available from Nati...

Page 5: ...lame Return the control motor to the low fire position Check the combustion air differential pressure as discussed in Step 2 Gas pressure drop across the burner will be too low to read reliably but th...

Page 6: ...e Trains The pilot gas valve train should be connected as close as possible to the pilot adjusting cock Flame Rod and U V Scanner See Figure 4 When mounting a UV scanner use short pipe nipples to insu...

Page 7: ...t 1 2 N P T Air Valve Shaft Tap D Air Switch Connection 1 8 N P T Blower Ignition Plug 750 1250 150000 5 1500 2000 150000 12 DETAIL Peepsight 1 2 N P T Spark Plug 1 2 N P T Flame Rod or UV Scanner 1 2...

Page 8: ...matic gas valves including the main gas butterfly and the pilot gas cock Combustion Air Blower Start the blower and check the impeller for correct rotation If it s running back wards have a qualified...

Page 9: ...matic gas valves including the main gas butterfly and the pilot gas cock Combustion Air Blower Start the blower and check the impeller for correct rotation If it s running back wards have a qualified...

Page 10: ...t 1 2 N P T Air Valve Shaft Tap D Air Switch Connection 1 8 N P T Blower Ignition Plug 750 1250 150000 5 1500 2000 150000 12 DETAIL Peepsight 1 2 N P T Spark Plug 1 2 N P T Flame Rod or UV Scanner 1 2...

Page 11: ...e Trains The pilot gas valve train should be connected as close as possible to the pilot adjusting cock Flame Rod and U V Scanner See Figure 4 When mounting a UV scanner use short pipe nipples to insu...

Page 12: ...lame Return the control motor to the low fire position Check the combustion air differential pressure as discussed in Step 2 Gas pressure drop across the burner will be too low to read reliably but th...

Page 13: ...portionator damage Limit Controls Limit controls and safety equipment should comply with current NFPA Standard 86 and all applicable local codes and or standards NFPA Standards are available from Nati...

Page 14: ...4 9 6 1 7 3 7 5 4 5 7 4 8 1 9 8 12 0 9 1 8 7 12 3 3 0 3 9 4 4 4 0 4 5 6 4 7 2 4 5 6 5 7 0 8 5 10 7 8 1 7 9 11 4 1 0 2 8 3 4 3 0 3 5 5 4 6 1 4 0 5 8 5 9 6 9 9 4 7 0 7 0 10 5 0 0 2 3 2 8 2 5 2 9 4 9 5 5...

Page 15: ...t See Figure 6 for filter element replacement Spark Plug Flame Rod Replacement Ignition plugs and flame rods wear out over long periods of normal burner opera tion For Ratiomatic burners the part numb...

Reviews: