24
P0016-LI-02.01
3. System Configuration
This section covers programming of the system timers, counters,
hardware, control timers, banner text, voice options and links.
System Timers
The system timers control global system timing and delay
operation.
Locations:
3101
- AC Fail Delay.
3102
- ATS Fault Delay.
3103
- Zone Response Time.
3104
- Abort Delay.
3105
- Battery Test Period.
3106
- Battery Test Duration.
3107
- Zone Soak Test Time.
3108
- Double Knock Delay.
3109
- Service Interval.
3110
- Confirmation Period.
3111
- Pulse 1 Time.
3112
- Pulse 2 Time.
3113
- Pulse 3 Time.
3114
- Delay 1 Time.
3115
- Delay 2 Time.
3116
- Delay 3 Time.
3117
- Warning Delay.
Entry Mode:
Number Entry (see page 18).
01 AC Fail Delay
This timer is used to delay (0-255 minutes) the audible
annunciation from the keypads and internal sounders following
an AC mains failure. Default = 30 minutes.
02 ATS Fault Delay
This timer is used to delay (0-255 minutes) the audible
annunciation from the keypads and internal sounders following a
ATS fault (telephone line fault). Default = 30 minutes
03 Zone Response Time
This timer is used to control the response (0-255 x 10ms) of
zones programmed with the “Fast Response” attribute. Default =
750 milliseconds.
04 Abort
Delay
This timer is used to control abort delay period (0-255 x seconds).
When an intruder alarm is generated, this timer is started and if
the system is disarmed before the timer expires an “Alarm Abort”
event is generated. This event can be signalled to the alarm
receiving centre. Default = 180 seconds.
05 Battery Test Period
This timer is used to control frequency (0-255 hours) at which the
standby battery is load tested. Default = 24 hours.
06 Battery Test Duration
This timer is used to control the duration (0-255 seconds) of the
standby battery load test. Default = 10 seconds.
07 Zone Soak Test Time
This timer is used to control the duration (0-255 days) of the zone
soak test. The timer is automatically started after a zone is put on
test. Default = 14 days.
08 Double Knock Delay
This timer controls the duration (0-255 seconds) of the double
knock delay. The double knock delay is used to control the
operation of zones programmed with “Double Knock” attribute,
see page 20. Default = 30 seconds.
09 Service
Interval
This timer controls the frequency (0-255 weeks) in which a
“Service Required” event is generated. Default = 0 weeks.
10 Confirmation
Period
This timer controls the duration (0-255 minutes) in which a
confirmed alarm event can be generated. When the system is
armed and an intruder alarm is generated (first alarm), this timer
is started. If a second, but different zone activates an intruder
alarm before the timer expires, a confirmed alarm event is
generated. Default = 45 minutes.
11 Pulse 1 Time
This timer controls the active duration (0-255 seconds) of outputs
programmed with the “Pulse 1” attribute. Default = 10 seconds.
12 Pulse 2 Time
This timer controls the active duration (0-255 seconds) of outputs
programmed with the “Pulse 2” attribute. Default = 30 seconds.
13 Pulse 3 Time
This timer controls the active duration (0-255 minutes) of outputs
programmed with both the “Pulse 1” and “Pulse 2” attributes.
Default = 10 minutes.
14 Delay
1
Time
This timer controls the switch on delay (0-255 seconds) of outputs
programmed with the “Delay 1” attribute. Default = 10 seconds.
15 Delay
2
Time
This timer controls the switch on delay (0-255 seconds) of outputs
programmed with the “Delay 2” attribute. Default = 30 seconds.
16 Delay
3
Time
This timer controls the switch on delay (0-255 minutes) of outputs
programmed with both the “Delay 1” and “Delay 2” attributes.
Default = 10 minutes.
17 Warning
Delay
This timer controls the delay (0-255 seconds) in which zones
programmed as “Warning” must remain active before a warning
tone is generated. Default = 60 seconds.
System Counters
The system counters are used to limit the number of times a
function or feature can be carried out.
Locations:
3201
- Auto Rearm Counter.
3202
- Number of Remote Resets.
3203
- Count Warning.
3204
- Count Logging.
Entry Mode:
Number Entry (see page 18).
01 Auto Rearm Counter
This counter controls the number of times (0-255) a zone can
rearm during an armed period. Once a zone has reached its rearm
limit, it is locked out so that it cannot cause further alarm
activations during the same armed period. Default = 3.
02 No of Remote Resets
This counter controls the number of times (0-255) the UDL
software can be used to reset the system remotely before an
engineer must attend site. Default = 0.
03 Count
Warning
This counter controls the number of times (0-255) that a zone
must activate, before triggering the corresponding “Zone ##
Count” output. Default = 0.
02 Count
Logging
This counter controls the number of times (0-255) that a zone
must activate, before logging a “Zone Count ##” event in the
system log. Default = 0.