background image

8

Eclipse Extern-A-Therm Recuperators, Design Guide 540, 3/9/2009

Figure 3.2. 

Figure 3.3. 

Typical Air Pipe Work

The schematic, Figure 3.4, shows a typical air control
scheme. This uses one control valve to control the
combustion air, eductor air and dilution air. As the burners
turn down, the eductor air lowers to reduce the suction
and keep the furnace at the desired pressure. If dilution air
is necessary, this will also be reduced, so as not to
excessively cool the exhaust gas. A more sophisticated
control, Figure 3.5. This assumes that greater furnace
pressure control is required. The eductor air has a
separate control valve driven by the furnace pressure
control.

More details of the combustion circuits and methods of
controlling the air and gas can be found in Design Guide
206 covering ThermJet Burners for Preheated
Combustion Air.

Eductor Air Flow

Eductors are designed to overcome the exhaust gas
pressure drop through the recuperator. The eductor
airflows given in the datasheet are the flows required to
overcome the exhaust pressure drop at the maximum
rating of the recuperator and an inlet exhaust temperature
of 1900°F (1037°C). The entrainment air flow required will
be different at other capacities or exhaust temperatures.

Cleaning the Recuperator

Dirt or other substances in the exhaust can accumulate on
the outside of the recuperator tubes. Units can be cleaned
with steam, compressed air, or any other method that
accomplishes the task without damaging the insulation.

Exh

a

ust

Eductor

Recuper

a

tor &

Insul

a

ted Housin

g

Over -

te

m

per

a

ture

Ther

m

ocouple

Dilution

A

ir

Eductor

A

ir

S

upport

S

tructure

By Custo

m

er

Eductor

Eductor

A

ir

Flue

Flue

Bre

ak

Summary of Contents for 300 MA

Page 1: ...Eclipse Extern A Therm Recuperators Models 300 MA 2500 MA Design Guide 540 3 9 2009...

Page 2: ...duct whether due to breach of warranty negligence strict liability or otherwise is limited to the furnishing of replacement parts and Eclipse will not be liable for any other injury loss damage or exp...

Page 3: ...5 Safety Warnings 5 Capabilities 5 Operator Training 5 Replacement Parts 5 System Design 6 Furnace Temperature Limits 6 Flue Gas Restrictions 6 Recuperator Sizing 7 Dilution Air 7 Number of Recuperat...

Page 4: ...ease of installation and efficient use of existing pipe work The housings are internally insulated there is no need for additional external insulation Figure 1 1 Extern A Therm Recuperator Audience Th...

Page 5: ...ribed herein without written advice from Eclipse Capabilities Adjustment maintenance and troubleshooting of the mechanical and the electrical parts of this system should be done by qualified personnel...

Page 6: ...ld destroy the recuperator A high temperature protection limit switch must be fitted to ensure flue temperatures do not exceed 2100 F The recuperator must be positioned so that it will not be exposed...

Page 7: ...w is controlled on the cold side of the recuperator All the subsequent instructions and descriptions are written with this assumption If it is required that a single Extern A Therm recuperator will pr...

Page 8: ...lling the air and gas can be found in Design Guide 206 covering ThermJet Burners for Preheated Combustion Air Eductor Air Flow Eductors are designed to overcome the exhaust gas pressure drop through t...

Page 9: ...ical Piping for Greater Furnace Pressure Control Eductor Air Combustion Air Dilution Air if Required Exhaust Gas Preheated Combustion Air to Burners Preheated Combustion Air to Burners Eductor Air Com...

Page 10: ...5 x 10 3 millimeter mm inch in 3 94 x 10 2 MJ Nm BTU ft standard 2 491 x 10 2 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millime...

Page 11: ...Offered By Power Equipment Company 2011 Williamsburg Road Richmond Virginia 23231 Phone 804 236 3800 Fax 804 236 3882 www peconet com...

Reviews: