Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
8
I
NTRODUCTION
Specifications
This section gives a detailed overview of Bi-Flame specifications and
dimensions.
2
Specifications
Parameter
Description
Supply
•120 VAC (+10%, -15%), 50/60 Hz standard.
Internal
power
consumption:
24VA
Temperature Ranges
Unit
Model Nos.
Temperature Range
Bi-Flame
6500
-40˚
to
+60˚C
(-40˚
to
+140˚F)
90˚ U.V. Scanner
5600-90A
-20˚ to +60˚C (0˚ to 140˚F)
U.V. Scanner
5600-91
-40˚ to +125˚C (-40˚ to +257˚F)
NEMA4 UV Scanner
5600-91N4
-20˚ to +125˚C (0˚ to 257˚F)
Self-Check
U.V.
5602-91
-40˚
to
+60˚C
(-40˚
to
+140˚F)
Remote
Display
6000D
0˚
to
50˚C
(32˚
to
122˚F)
Flame Failure Response
• 3 seconds ±0.5 seconds.
TFI/Pilot Interrupt
• 5, 10 or 15 seconds selectable.
Purge Time
• Modulating: selectable from 0-225 seconds in 15 second increments,
or 0-15 minutes in 1 minute increments
• Process: selectable from 0-15 minutes in 1 minute increments,
or 0-60 minutes in 4 minute increments.
Contact Ratings @ 120 VAC
Function
Affected Terminals
Inductive Load Resistive Load
(maximum total connected
Output Relay
J2-4 through J2-8
1/3 HP
10 amps
load not to exceed 15 amps)
Output Relay
J2-3
1/2 HP
15 amps
Modulation
J3-1 through J3-4
1/3 HP
10 amps
Approvals
• UL Recognized; File MP1537 (category MCCZ2)
• FM Approved; J.I. 2Y3A5.AF (class 7610)
• CSA Certified; File 007989-0-000 (class 2632-01, 2642-01)
Shipping Weight
• 2.7 kilograms (6 lbs.)