Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
41
Table 10.2
Remote Display Diagnostic Messages (continued)
MESSAGE
TYPE
EXPLANATION
Lockout
Main flame was not established during the main burner trial for ignition.
Lockout
Main valve has been energized and main flame proven during trial
for ignition.
Status
Pilot valve (strip J2, terminal 5) is de-energized and main flame is on.
Lockout
Main valve proof-of-closure is open before startup or after burner
shutdown.
Lockout
Pilot flame was not established during the pilot trial for ignition.
Status
Pilot flame is proven; transformer is de-energized; remaining
countdown for pilot trial for ignition is “XX”.
Status
Pilot valve and ignition transformer are energized; countdown for
pilot trial for ignition begins at “XX”.
Lockout
An external source of voltage is present on the ignition, pilot or
main output terminals.
Status
15 second post purge is started on burner shutdown; “XX” shows
countdown.
Lockout
DIP switch improperly set or changed during cycle.
Status
Modulating motor is sent to high fire; “XX” shows purge countdown.
Status
Part of the optional history log which records the total number of
operating cycles and the last lockout messages up to a maximum
of 10.
Lockout
Internal relay(s) fail initial check. Check ratings. If lockout still oc-
curs after overload is eliminated, replace control.
Status
Control has completed internal safe-start check.
Status
Combustion air switch is closed before start-up or after shut-
down; control holds start-up until switch re-opens; if interlocks
close before switch opens, alarm will energize in 30 seconds.
Lockout
Same conditions as above, except the interlocks closed for 30 sec-
onds before the switch re-opened, causing a lockout and the alarm.
MAIN # ( ) FAILED
MAIN FLAME ON
MAIN FLAME ON
PILOT OFF
MAIN VALVE FAIL
LKOUT XXXX:XX:XX
PILOT FLAME FAIL
LKOUT XXXX:XX:XX
PILOT ON
XX
PILOT TRIAL FOR
IGNITION
XX
PLT/MVL ENERGIZ.
XX:XX:XX LOCKOUT
POST PURGE
XX
PROGM SWITCH ERR
LKOUT XXXX:XX:XX
PURGE AT HIGH
FIRE XX
RECORD #X
RELAY FAIL
LKOUT XXXX:XX:XX
SAFE START OK
UNSAFE AIR SHORT
UNSAFE AIR SHORT
LKOUT XXXX:XX:XX