
Version 2.02 15.05.2007
Menu Structure of VS 3000
106
Messages
POS: XXXXX
Entry
Default / Dimension
NT
LT
Dim.
Meas. error tod
X
Outdoor temperature measuring loop error
-, 0..2
2
2
-
Meas. error tr
X
Room temperature measuring loop error
-, 0..2
2
2
-
Meas.err.hunid.
X
Humidity sensor measuring loop error
-, 0..2
2
2
-
Power failure
X
Start following power failure
-, 0..2
0
0
-
First start
X
Controller start
-, 0..2
2
2
-
Burst disc
X
Bursting disk input actuated
-, 0..2
-
-
-
External alarm
X
External alarm input actuated
-, 0..2
-
2
-
I/O module error
X
SIOX I/O module failure
-, 0..2
1
1
-
Service mode
X
Service mode activated
-, 0..2
0
0
-
Comp/cond unload
X
External unload activated
-, 0..2
0
0
-
Load shed
X
Compressor disabled by load shedding
-, 0..2
0
0
-
Low liq. level
X
Low liquid level cutout tripped
-, 0..2
2
2
-
RAM error
X
Internal data memory fault
-, 0..2
1
1
-
EEPROM error
X
EEPROM (parameter memory) fault
-, 0..2
2
2
-
RTC error
X
Real-time clock fault
-, 0..2
2
2
-
Setpoint changed
X
Setpoint changed
-, 0..2
0
0
-
Max. speed F
X
Threshold value for speed adjuster exceeded.
-, 0..2
0
0
-
Battery voltage
X
Internal battery fault
-, 0..2
2
2
-
Manual OFF
X
Compressor OFF by manual switch
-, 0..2
0
0
-
Manual ON
X
Compressor ON by manual switch
-, 0..2
0
0
-
Emerg. working
X
Emergency operating mode
-, 0..2
0
0
-
HP cutout D2D Z1
X
High-pressure cutout for discharge gas defrosting
Z1 cases
-, 0..2
2
2
-
HP cutout D2D Z2
X
High-pressure cutout for discharge gas defrosting
Z2 cases
-, 0..2
2
2
-
HPcutout D2D Z2R
X
High-pressure cutout for discharge gas defrosting
Zs coldrooms
-, 0..2
2
2
-
Disable D2D Z1
X
Disable discharge gas defrosting Z1
-, 0..2
0
0
-
Disable D2D Z2
X
Disable discharge gas defrosting Z2
-, 0..2
0
0
-
Disable D2D Z2R
X
Disable discharge gas defrosting Z2 coldrooms
-, 0..2
0
0
-
Fault D2D Z1
X
Discharge gas defrosting fault Z1
-, 0..2
2
2
-
Fault D2D Z2
X
Discharge gas defrosting fault Z2
-, 0..2
2
2
-
Fault D2D Z2R
X
Discharge gas defrosting fault Z2 coldrooms
-, 0..2
2
2
-
Sens type change
X
Sensor matching changed
-, 0..2
0
0
-
Comp auto disabl
X
Automatic compressor disable
-, 0..2
2
2
-
too many starts/h
X
Compressor short-cycling (LP combined control-
ler)
-, 0..2
2
2
-
no load level
X
No load level received (t0 shift)
-, 0..2
2
2
-