Parameter List and Menu Structure of VS 300
102
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
8.1.5
Parameter List S2: Setpoints Basic Parameters - Night Operation
CL1
CL2
Function/
Description
Range
Default
Dim.
Displayed / Condition
NT
LT
HP
S210
S250
Second setpoint t
max
-50..45
-10
-38
25
°C
Minimum of stage must be defined in CL:
CL1:
S301
>
0
/ CL2:
S331
>
0
S211
S251
First setpoint t
min
-50..35
-16
-40
25
°C
(1), and temperature shift must be activated in CL:
CL1: S310 = 1 / CL2: S340 = 1
S212
S252
first setpoint
t-adjust.
_max
16..45
25
25
30
°C
S213
S253
first setpoint
t-adjust.
_min
0..20
15
15
0
°C
S214
S254
Neutral zone 2nd SP
1..10
4
4
6
K
Minimum of stage must be defined in CL:
CL1:
S301
>
0
/ CL2:
S331
>
0
S215
S255
Control constant 2nd
SP
1..10
10
7
10
S216
S256
Activate humidity shift
0: nicht
aktiv
1: aktiv
0
0
0
-
(1), and humidity shift must be activated in CL:
CL1: S311 = 1 / CL2: S341 = 1
Parameter List S1 and S2:
To change values set access level to setpoint adjustment enabled (Pa
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...