Parameter List and Menu Structure of VS 300
101
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
3)
Values of more than 4 digits (e.g. 21900 operating hours) are displayed with the help of the relay stage
operating and status indicators (LED flashing) as follows:
Value = Value of LED display [0 - 9999] + (Number of flashing operating and status indicator LED * 10000)
4)
Status of digital inputs I1 - I4 is shown on the 4-digit LED display as follows, from left to right:
1st digit = Input 1
2nd digit = Input 2
3rd digit = Input 3
4th digit = Input 4
5)
Status of alarm outputs A1 - A2 is shown on the 4-digit LED display as follows, from left to right:
1st digit = 0
2nd digit = 0
3rd digit = Alarm output 1
4th digit = Alarm output 2
Parameter List A:
Entries cannot be made (actual values)!
Exception:
Parameter A060 only (used
to enable access level)!
8.1.3
Parameter List S1: Overview of Main Setpoints - Day/Night Operation
CL1
CL2
Function/
Description
Range
Default
Dim.
Displayed / Condition
NT
LT
HP
S100
S110
First setpoint t
max
-50..45
-12
-38
25
°C
(1)
S101
S111
First setpoint t
min
-50..35
-16
-40
25
°C
(1), and temperature shift must be activated in CL:
CL1: S310 = 1 / CL2: S340 = 1
S102
S112
Second setpoint t
max
-50..45
-10
-38
25
°C
(1)
S103
S113
First setpoint t
min
-50..35
-14
-36
25
°C
(1), and humidity shift must be activated in CL:
CL1: S310 = 1 / CL2: S340 = 1
8.1.4
Parameter List S2: Setpoints Basic Parameters - Day Operation
CL1
CL2
Function/
Description
Range
Default
Dim.
Displayed / Condition
NT
LT
HP
S200
S240
First setpoint t
max
-50..45
-12
-38
25
°C
Minimum of stage must be defined in CL:
CL1:
S301
>
0
/ CL2:
S331
>
0
S201
S241
First setpoint t
min
-50..35
-16
-40
25
°C
(1), and temperature shift must be activated in CL:
CL1: S310 = 1 / CL2: S340 = 1
S202
S242
first setpoint
t-adjust.
_max
16..45
25
25
30
°C
S203
S243
first setpoint
t-adjust.
_min
0..20
15
15
0
°C
S204
S244
Neutral zone 1st SP
1..10
4
4
6
K
Minimum of stage must be defined in CL:
CL1:
S301
>
0
/ CL2:
S331
>
0
S205
S245
Control constant 1st SP
1..10
10
7
10
S206
S246
Activate humidity shift
0: nicht
aktiv
1: aktiv
0
0
0
-
(1), and humidity shift must be activated in CL:
CL1: S311 = 1 / CL2: S341 = 1
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...