Firmware V3.00
05.08.2019
15/100
3.2 Hardware
The temperature recording controller is housed in a plastic casing for DIN rail mounting. Up to 99 case
controllers can be used within the E*LDS system. As required, a BT 300 x Operator Interface and up to 4 BT 30
Temperature Displays can be connected. For a firmware update, the controller can be connected to a laptop or
PC via the USB interface. The application range of the temperature recording controller is described in more
detail in chapter
. The following diagram illustrates the system architecture of the UA 410 L AC
temperature recording controller (complete):
Ports
•
CAN bus: Communication in E*LDS-System, new version
•
DISPLAY: Connection for BT 300x Operator Interface and up to four BT 30 Temperature Displays
•
CI 320: Communication with LDSWin software / Connection to the legacy system CI 320
•
USB: For conducting a firmware update
Inputs/outputs
•
4 digital inputs 230 V AC, floating
•
10 analog inputs Connection for two-wire NTC temperature sensors
•
Only UA 410 AC:2 x analogue inputs 4..20 mA - currently without function
Outputs
•
3 relay output 230 V AC / 6 A (changeover)
•
4 relay outputs 230 V AC / 6 A (N.O.)
•
2 transistor outputs 24 V DC / 50 mA (for lighting control and frame heater)
•
Only UA 410 AC:2 x analogue outputs 0..10 V DC - currently without function
Real-time clock
•
Battery-backed, lithium cell
For precise details of the UA 410 L AC see chapter
. The connection and terminal
configurationsare described in the chapter
Pin and Terminal Assignments of UA 410 L
.