Firmware: V2.18 / V--
26.10.2022
76/119
9.3.1 Settings using DIP switch S1
There are two types of coding switches on
DIP switch S1
:
1. Coding switches 1..4 - Freely programmable in CODESYS.
These are read in
during the runtime
and act on the controller immediately after adjustment. The coding
switches are freely available to the programmer of the application. The programmer defines the meaning of the
coding switches, how they should be used.
Coding switches 1..4
Switch position
Function
ON
Freely programmable
OFF
2. Coding switches 5..7 - Hard-coded into the firmware of the controller.
These do not take effect
until after
, i.e. not until after a short interruption of the power supply of the
controller.
Coding switch 5
Coding switch 5 sets the transfer rate on the CAN bus. Up to now, a transmission rate of only 50 kbit/s was
possible on the CAN bus (factory setting). By flipping the coding switch to "ON" you get 5 times the transfer rate
(250 kbit/s). The High Speed mode of the Combi Gateway provides this transfer rate
Coding switch 5
Switch position
Function
ON
250 kbit/s (High Speed)
OFF
50 kbit/s (factory setting)
ATTENTION - ONLY CI 3x00
If the setting is incorrect, no communication can be established with the CAN bus. When using the high
speed mode, the store computer CI 3x00 must be configured accordingly. The following requirements
must be met:
The store computer
must
have the firmware V5.0 or higher and the parameter
"CAN Bus Fast"
(menu
6-1-1) must be set to
Yes
.