System Overview 

CabLite® ECO is a general downlighting system for use in passenger, residential and freight elevator 
cabs operating from one to twelve downlight.  CabLite® ECO high output, long life low voltage LED 
downlights provide general interior lighting that meets or exceeds ASME A17.1, local, state and federal 
codes. 
There are 3 options for the CabLite ECO system: 

 

ECO 

 

ECO with dimming 

 

ECO with dimming and emergency lighting 

6.1

 

Downlights 

Each downlight is equipped with 2 connectors (located on the top of the can) for chaining up to 12 lights 
together. The 2 connectors are interchangeable so it does not matter which cable is connected to it.  See 
Figure 1 - Downlight Connectors.  Each downlight has 2 spring loaded clips that hold the light tight to the 
ceiling panel. 
 

 

Figure 1 - Downlight Connectors 

 

6.1.1

 

ECO Downlight Specifications 

 
Operating voltage 24VDC  

 

5000K 

4000K 

3000K 

# of LEDs 

Color Temp 

5000K 

4000K 

3000K 

Power Consumption  

8W 

8W 

8W 

CRI 

80 +/-5 

85 +/-5 

85 +/-5 

 

6.2

 

CabLite ECO 

The CabLite ECO is our very basic lighting system consisting of the following: 

 

1 to 12 downlights  

 

24VDC power supply (mounted in gang box) 

 

One 8’ cable for connecting first downlight 

 

One 4’ cable for each additional downlight 

 

Gang box and cover 

Summary of Contents for CabLite ECO 3000K

Page 1: ...ELECTRONIC CONTROLS INC 7073 NORTH ATLANTIC AVE CAPE CANAVERAL FL 32920 WWW ECIAMERICA COM 800 633 9788 CabLite ECO Installation Manual REV 4 1 DATE 1 17 2018 MANUAL NUMBER 32 ...

Page 2: ...al FL 32920 800 633 9788 www eciamerica com P a g e 2 REV DATE DESCRIPTION 1 0 10 28 2013 Initial release 2 0 3 7 2014 Updated the manual 3 0 7 8 20014 Added Dimming Emergency board wiring 4 0 3 8 2017 New Manual format re write 4 1 1 17 2018 Added new logo and drawings with 10k pot and service loops ...

Page 3: ... and Emergency Lighting Option 8 6 4 1 CabLite ECO Emergency Board Connections 8 6 4 2 CabLite Emergency Board LEDs 9 7 Installation 9 7 1 Flat Bezel Downlight Dimensions 10 7 2 Raised Bezel Downlight Dimensions 10 7 3 CabLite ECO Wiring Diagram 11 7 4 CabLite ECO w Dimming Wiring Diagram 11 7 5 CabLite ECO w Dimming Emergency Wiring 12 8 Trouble Shooting 14 8 1 One Light Does Not Turn On 14 8 2 L...

Page 4: ... 1 Safety code for Elevators and Escalators and the codes of the National Electrical Manufacturer s Association NEMA There may be local regulatory or government offices that can also help determine which codes and standards are necessary for safe installation and operation Equipment damage or serious injury to personnel can result from failure to follow all applicable codes and standards We do not...

Page 5: ...o have available Before connecting electrical wiring take precautions to prevent accidents from happening to yourself and others around you ALWAYS CONSIDER SAFTY FIRST Wear a hard hat when working in the hoist way Wear safety glasses or goggles when using power tools Always wear protective gloves when installing or removing access covers conduits wireway or electrical devices When working on car c...

Page 6: ...Downlights Each downlight is equipped with 2 connectors located on the top of the can for chaining up to 12 lights together The 2 connectors are interchangeable so it does not matter which cable is connected to it See Figure 1 Downlight Connectors Each downlight has 2 spring loaded clips that hold the light tight to the ceiling panel Figure 1 Downlight Connectors 6 1 1 ECO Downlight Specifications...

Page 7: ...sted without having to access the car top The AC voltage input of the power supply Brown LINE Blue NEU is left free for the customer to decide how to connect Figure 8 CabLite ECO with Dimming Wiring shows wire nuts The 24VDC power supply output is prewired at the factory to the Dimmer Board The Dimmer board has a 12 cable prewired to the LIGHTING Output of the Dimmer board It has a two pin connect...

Page 8: ...ch connected to the STBY input pins 9 10 6 4 1 CabLite ECO Emergency Board Connections Refer to Figure 3 CabLite ECO Emergency Board Pin 1 IN is 24VDC input power RED Wire Pin 2 IN is 24VDC input BLACK Wire Pin 3 OUT is output for general power AC present Downlight String RED Wire Pin 4 OUT is output for general power downlight string BLACK Wire Pin 5 6 is for external potentiometer customer provi...

Page 9: ...ery is fully charged FAULT The fault LED lights when there is a problem with the battery Wrong voltage or not charging 7 Installation Be sure all power is turned off before starting installation Locate the positions where you want each downlight and drill the ceiling panels according to the specifications for your downlight listed in sections 7 1 and 7 2 Be sure there is a minimum 1 clearance betw...

Page 10: ...orth Atlantic Ave Cape Canaveral FL 32920 800 633 9788 www eciamerica com P a g e 10 7 1 Flat Bezel Downlight Dimensions Figure 4 Flat Bezel Downlight Dimensions 7 2 Raised Bezel Downlight Dimensions Figure 5 Raised Bezel Downlight Dimensions Figure 6 Installation example ...

Page 11: ...wire on power supply AC IN neutral Blue wire on power supply DC OUT is RED wire of 8 cable DC OUT is BLACK wire of 8 cable Route the 8 cable to the first downlight and connect remaining downlights with 4 cables The two connectors on the downlights are interchangeable so cable connection does not matter Once wiring is complete and cover is on power supply box apply power to lighting system Check th...

Page 12: ...wer to lighting system and adjust brightness using the potentiometer on the Diming board See Figure 2 Dimmer Board When complete install cover to power unit 7 5 CabLite ECO w Dimming Emergency Wiring Figure 9 CabLite ECO w Dimming Emergency Wiring As previously mentioned the CabLite system power supply and dimming board are pre wired from the factory The BATTERY negative terminal is prewired to th...

Page 13: ...re than two will shorten the emergency lighting time With all downlights connected remove the plastic cover from the POS terminal of the battery and connect RED wire from control board to battery POS terminal The EMERGENCY downlights should light at this time Apply AC power to CabLite system All downlights should light Adjust the brightness of the downlights through the potentiometer on the contro...

Page 14: ...4VDC a If no 24VDC check for 24VDC at IN i If no 24VDC at IN then check for 120VAC at power supply input ii If 120VAC present replace power supply b If 24VDC present at IN then replace Control board 3 If 24VDC present at OUT then check continuity of 8 cable and replace if necessary 8 4 No Emergency Lights with AC loss Emergency light option 1 Check connection between control board and first emerge...

Reviews: