background image

7

Installing Wireless Devices

Careful planning is needed when locating the receivers and transmitters based 

on the construction materials in the space and possibility of tenant’s furniture 

disrupting the transmissions.
The sensor should be installed in the space where the receiver is mounted. The 

signal will travel through some material barriers.
Refer to the tables below for range considerations with building materials that 

reduce the radio signal power.

Material

Attenuation

Wood

0 - 10%

Plaster

0 - 10%

Glass

0 - 10%

Brick

5 - 35%

MDF

5 - 35%

Ferro concrete

10 - 90%

Metal

90 - 100%

Aluminum 

90 - 100%

Wireless System Layout Hints

•  Avoid locating transmitters and 

receivers on the same wall.

•  Avoid locating transmitters and receivers where the telegrams must 

penetrate walls at acute angles. This increases the material the telegram 

must pass through reducing the signal power.

•  Avoid large metal obstructions as they create radio shadows. Place 

receivers in alternate locations to avoid the shadow or use repeaters to go 

around the obstacle.

•  Do not locate receivers close to other high frequency transmitters.
•  Leave at least 3’ between the receiver and any other source of interference 

including, ballasts, LED drivers, computers, video equipment, Wi-Fi/LAN 

routers, GSM modems and monitors.

Material

Range Typical

Line of sight

80’ (24m) corridors

Line of sight

150’ (46m)open 

halls

Plasterboard

80’ (24m) through 

3 walls

Brick

33’ (10m) through 

1 wall

Ferro concrete 33’ (10m) through 

1 wall

Ceiling

Not Recommended

Summary of Contents for TAP-21C

Page 1: ...k Ambient Photo sensor also referred to as the sensor in this guide is a wireless energy harvesting sensor that monitors light levels within interior spaces and transmits the value to lighting control...

Page 2: ...2 Page Left Blank Intentionally...

Page 3: ...3 Supply Voltage 0 5 1V linear n 0 255 Daylight Harvesting The sensor will repeatedly broadcast a telegram on a timer heart beat timer The time period adjusts automatically to the ambient light levels...

Page 4: ...foot candles or 1024 lux 100 foot candles The factory default is 512 lux 3 Press the rear mounting plate back into position Installing or Replacing the Start Assist Battery The battery is not require...

Page 5: ...rs 5 826 83 9 0 hours 91 25 hours The time to fully charge is based on the storage capacitor charging from a non operational condition Discharge time indicates how long a fully charged sensor will ope...

Page 6: ...ng the test button for 6 seconds Commissioning Test Mode This mode accelerates the time period between transmissions of the current light level to every 10 seconds for a duration of 5 minutes regardle...

Page 7: ...ers and receivers on the same wall Avoid locating transmitters and receivers where the telegrams must penetrate walls at acute angles This increases the material the telegram must pass through reducin...

Page 8: ...se undesired operation IC RSS 210 315MHz and 902 MHz models only Contains IC 5713A STM300C or 5713A STM300U Construction Type Conformity Certificate 928 MHz model only TCM 410J complies with the Japan...