Echoflex Installation Guide

Ceiling Vacancy-Occupancy Sensor

Key Timers

The

Audio Enabled Timer

defines the maximum duration that audio

sensing is active. Each PIR detection resets the Audio Enabled Timer. The
timer setting is 60 minutes and is not configurable.

The

Sensor Occupancy Timer

defines the time that detection, PIR or

audio sensing, is required to keep the audio active. Each audio or PIR
event resets the timer. The default setting is 20 minutes and is
configurable.

The sensor transmits an occupied message to the controller:

Every 100 seconds, or

Immediately when a change to the occupied state is detected

Echoflex controllers also have a configurable occupancy timer that
controls when the lights shut off after a period of vacancy. See the
controller’s Configuration Guide for details on setting up timers and
occupancy or vacancy modes of control.

Dual Technology Models

When both PIR and audio sensing are enabled, the following logic is used:

When the space is occupied, PIR and audio detection can reset both
the sensor’s Occupancy Timer and the controller’s Occupancy Timer.

When the space is vacant and all timers have expired, only PIR
detection or manual control can change the state to occupied, if the
sensor is configured for occupancy.

When audio is detected in an occupied space, the sensor’s
Occupancy Timer is reset, but not the Audio Enabled Timer; it expires
after 60 minutes or is reset by PIR detection.

A vacancy message is sent after 20 minutes (default) of no detection,
then 40 seconds later the audio is disabled. The 40-second grace
timer allows an occupant sufficient time to use sound to reset the
sensor’s Occupancy Timer.

PIR Sensing Only

For PIR sensing only, the following logic is used:

When the space is occupied, PIR detection and manual control can
keep the lights ON and reset the controller’s Occupancy Timer.

When the space is vacant and the controller is configured for

occupancy

, a PIR detection or manual control can change the state

to occupied.

When the space is vacant and the controller is configured for

vacancy

, only manual control can change the state to occupied.

A vacancy message is sent after 200 seconds of inactivity, and then
subsequent messages are sent every 1000 seconds.

Ceiling Vacancy-Occupancy Sensor

Page 4 of 12

Echoflex

Summary of Contents for RVS-A-xW Series

Page 1: ...es The vacancy ceiling sensor RVS has two solar cells to harvest energy when the lights are ON while the occupancy ceiling sensor RCS is battery powered to support auto ON occupancy sensor application...

Page 2: ...to block off specific areas See Lens Masking on page 5 Do not install within 2 5 m 8 ft of an HVAC airflow duct or vent For the solar powered RVS model before linking the sensor expose it to a good li...

Page 3: ...uble sided Tape or Velcro 1 Cut two lengths of tape not provided to the appropriate size and adhere one side to the mounting plate and the other to the ceiling 2 Press the sensor firmly in place Sensi...

Page 4: ...upancy Timer and the controller s Occupancy Timer When the space is vacant and all timers have expired only PIR detection or manual control can change the state to occupied if the sensor is configured...

Page 5: ...fer to the controller product documentation 3 Press the Teach button on the RVS RCS once to send a message An LED blinks to confirm a successful transmission 4 Deactivate Link mode on the controller b...

Page 6: ...ructions Light Level Test green LED Range Confirmation blue LED Walk Test red LED Sensor Setting red and blue LEDs LED Display green and red LEDs The menu times out after two minutes of inactivity Lig...

Page 7: ...inked controllers detected The test repeats every five seconds and runs for 50 seconds To exit before the time out press and hold the Teach button Walk Test The Walk Test verifies the boundaries or li...

Page 8: ...nks Occupancy Timer DT model only Note Echoflex dual tech sensors have a configurable Occupancy Timer that sends a vacancy message when expired If using another controller brand with a DT model you ma...

Page 9: ...when the green and red LEDs are both blinking 3 Press and hold the Teach button until the LEDs stop blinking to select LED Display 4 Press the Teach button to toggle between the two states Red LED bli...

Page 10: ...io communications Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipm...

Page 11: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 11 of 12 Echoflex...

Page 12: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 12 of 12 Echoflex...

Reviews: