To replace the battery:

1. Use your fingers to remove the cover, flexing it gently to release the

tabs that hold it in place. If you have difficulty, consider inserting a
small flatblade screwdriver under a release tab.

2. Use your finger to remove the old battery from the holder. Insert a

new battery with the + positive side facing up and press in place.

3. Replace the cover and press in place.

Tests and Settings

Use the

[Teach]

button and color LEDs to navigate the Tests and Settings

Menu. Remove the cover to access the

[Teach]

button located beside the

battery clip. The LEDs display through the front lens.

Note:

A battery is required to run tests or change settings. If you

cannot access the LED blink menu, replace the battery. See

Battery

Power on page 5

for installation instructions.

Light Level Test

(green LED)

Range Confirmation

(blue LED)

Walk Test

(red LED)

Sensor Setting

(red and blue LEDs)

LED Display

(green and red LEDs)

The menu times out after two minutes of inactivity.

Light Level Test

The Light Level Test quantifies the amount of energy produced by the
solar cells and confirms a good installation location.

1. Press and hold the

[Teach]

button until the green LED appears.

Release the button to enter the menu and display the first item,
blinking green LED.

2. Press and hold the

[Teach]

button again until the green LED stops

blinking. The green LED then repeats a number of blinks according to
the detected light level. If you move the sensor, it reevalutes the light
level every two seconds.

Blinks

Lux (Footcandles)

Charge Level

1

< 40 (< 3.7)

Not sustainable

2

40–65 (3.8–6)

PIR operational only

3

> 65 (> 6)

Dual-tech operational

The test repeats every two seconds and runs for 100 seconds. To exit
before the time-out, press and hold the

[Teach]

button for 10 seconds.

Ceiling Vacancy-Occupancy Sensor

Page 6 of 12

Echoflex

Summary of Contents for RCS-A-xW Series

Page 1: ...es The vacancy ceiling sensor RVS has two solar cells to harvest energy when the lights are ON while the occupancy ceiling sensor RCS is battery powered to support auto ON occupancy sensor application...

Page 2: ...to block off specific areas See Lens Masking on page 5 Do not install within 2 5 m 8 ft of an HVAC airflow duct or vent For the solar powered RVS model before linking the sensor expose it to a good li...

Page 3: ...uble sided Tape or Velcro 1 Cut two lengths of tape not provided to the appropriate size and adhere one side to the mounting plate and the other to the ceiling 2 Press the sensor firmly in place Sensi...

Page 4: ...upancy Timer and the controller s Occupancy Timer When the space is vacant and all timers have expired only PIR detection or manual control can change the state to occupied if the sensor is configured...

Page 5: ...fer to the controller product documentation 3 Press the Teach button on the RVS RCS once to send a message An LED blinks to confirm a successful transmission 4 Deactivate Link mode on the controller b...

Page 6: ...ructions Light Level Test green LED Range Confirmation blue LED Walk Test red LED Sensor Setting red and blue LEDs LED Display green and red LEDs The menu times out after two minutes of inactivity Lig...

Page 7: ...inked controllers detected The test repeats every five seconds and runs for 50 seconds To exit before the time out press and hold the Teach button Walk Test The Walk Test verifies the boundaries or li...

Page 8: ...nks Occupancy Timer DT model only Note Echoflex dual tech sensors have a configurable Occupancy Timer that sends a vacancy message when expired If using another controller brand with a DT model you ma...

Page 9: ...when the green and red LEDs are both blinking 3 Press and hold the Teach button until the LEDs stop blinking to select LED Display 4 Press the Teach button to toggle between the two states Red LED bli...

Page 10: ...io communications Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipm...

Page 11: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 11 of 12 Echoflex...

Page 12: ...Echoflex Installation Guide Ceiling Vacancy Occupancy Sensor Ceiling Vacancy Occupancy Sensor Page 12 of 12 Echoflex...

Reviews: