background image

7

Setting

Indication

High

Green LED blinking

Medium

Amber LED blinking

Low

Red LED blinking

To select a setting press and hold the test button for 6 seconds when the desired 

LED is blinking. To exit without saving, allow the test to time-out in 60 seconds or 

press the Link button to exit immediately without saving.

Wireless System Layout Hints

•  Avoid locating transmitters and receivers on the same wall.

•  Avoid locating transmitters and receivers where the telegrams must 

penetrate walls at acute angles. This increases the material the telegram 

must pass through reducing the signal power. 

•  Avoid large metal obstructions as they create radio shadows. Place 

receivers in alternate locations to avoid the shadow or use repeaters to go 

around the obstacle.

•  Do not locate receivers close to other high frequency transmitters. 

•  Leave at least 3’ between the receiver and any other source of interference 

including, ballasts, LED drivers, computers, video equipment, Wi-Fi/LAN 

routers, GSM modems and monitors. 

Summary of Contents for MOS-21 Series

Page 1: ...Motion Sensor with 868 MHz radio with high bay lens The package includes the occupancy sensor and installation guide MOS 21 Sensor Description The 21 series MOS sensor also referred to as the sensor...

Page 2: ...nds When the sensor awakens and no motion is detected the sensor transmits a vacancy telegram after 100 seconds 200 seconds total since the previous transmission The sensor will remain active until th...

Page 3: ...tly affect the receivers reception of the telegrams Before installing refer to the sections in the guide detailing the installation of wireless devices layout tips and test operation modes NOTE The se...

Page 4: ...the lens pops free 4 Choose a mounting method The sensor can be mounted With the screws and anchors not provided to a wall board ceiling Use a pencil to mark the mounting base key hole locations and r...

Page 5: ...accordance to the light level it is detecting see table below Light Level Test Indication Blinks Lux Foot candles Time to Fully Charge Discharge Time 0 0 0 below operating level n a 1 20 40 2 4 operat...

Page 6: ...nds 2 A quick press and release of the button at this point will allow you to select between test modes Pressing and releasing the test button scrolls through the LED indicators When the red LED is bl...

Page 7: ...me wall Avoid locating transmitters and receivers where the telegrams must penetrate walls at acute angles This increases the material the telegram must pass through reducing the signal power Avoid la...

Page 8: ...t notice Document 8DC 5492 Revision 1 4 8188M21 5492 1 Rev C Regulatory Statements FCC Part 15 231 315 and 902 MHz models only Contains FCC ID TCM300C or TCM300U The enclosed device complies with Part...