echoflex EREB-AP Installation Manual Download Page 7

Echoflex Installation Guide

Emergency Bypass Load Controller

Remote Activation Input

The EREB-AD offers a normally closed, dry contact input to accommodate
connection to a fire alarm panel, security system, or test switch. This
input ships from the factory with a blue wire loop (jumper) connected to
two of the top screw terminals. It is a complete loop that disables remote
activation. Do not remove this jumper unless you are installing a remote
triggering device.

Note:

Echoflex recommends that you power up and test your

system before connecting to a remote device. Do not remove the
jumper unless you are installing a remote triggering device.

The remote device that triggers the Emergency circuit ON must provide a
normally closed, maintained dry contact closure for fire alarms. When the
remote device is activated, the contact closure opens and the contacts
force the EREB-AD into the emergency ON state.

1. Power up and test your system before installing a remote activation

input to your EREB. See

Initial Test on page 8

.

2. Remove the wire loop jumper from the Remote Loop In and Remote

Loop Out terminals.

3. Connect the Remote Loop In and Remote Loop Out terminals on the

EREB-AD to the single pole contacts on the remote device or test
switch.

4. Go to

Remote Activation Test on page 9

to confirm the connection.

Configure a Time Delay

If your lighting requires a warmup period (for example, for high-intensity
discharge [HID] lamps), you can configure a time delay to keep the
emergency lighting on for a period of time after the normal power is
restored. The default time delay is zero. To configure a longer transition
time follow the steps below.

1.

Press the

[Option]

button on the EREB. Both the Status and

Remote LEDs will blink to indicate the current time delay
configured.

2.

Press and release the

[Option]

button to cycle through the
settings, and stop when the
blink pattern matches the
setting you want.

3.

Wait 10 seconds for the EREB
to save the setting and resume
normal operation.

No. of Blinks

Time Delay

1 blink

no delay (default)

2 blinks

10 seconds

3 blinks

30 seconds

4 blinks

10 minutes

5 blinks

15 minutes

Emergency Bypass Load Controller

Page 7 of 12

Echoflex

Summary of Contents for EREB-AP

Page 1: ...operation The EREB ensures a lights on override by using a normally closed emergency contact closure that interfaces with fire alarm and emergency systems The EREB is available in two models to provi...

Page 2: ...e c blage du courant alternatif v rifiez que les disjoncteurs pour l alimentation normale et pour l alimentation de secours sont en position d arr t et suivez les proc dures de v rouillage tiquetage p...

Page 3: ...y to the exterior of the junction box or panel either at the electrical lighting load or before the loads in the circuit See Examples of Use on page 10 Two sets of wire bundles are provided on the top...

Page 4: ...ow for wiring instructions 7 Replace the cover plate and restore power to the circuits Wiring Diagram Emergency Bypass Load Controller EREB AP Remote LED Option Button Status LED Emergency Power In Bl...

Page 5: ...ect normal sense and emergency power wires Four screw terminals on the top of the device are used for the following connections The two terminals on the left have a factory installed wire loop jumper...

Page 6: ...nnect to the terminals labeled 0 10 V FLO See Examples of Use on page 10 for more information 6 Are you are installing a remote triggering device to remotely activate the emergency circuit No Go to In...

Page 7: ...o your EREB See Initial Test on page 8 2 Remove the wire loop jumper from the Remote Loop In and Remote Loop Out terminals 3 Connect the Remote Loop In and Remote Loop Out terminals on the EREB AD to...

Page 8: ...ghting is not required 4 Confirm the automatic emergency On functionality by turning Off the circuit breaker in the normal panel The connected emergency lighting should immediately turn On again and t...

Page 9: ...ntrol circuit thereby illuminating the load and bypassing the normal control signal to the load In a properly operating system the load should illuminate upon pressing the Test button Remote Activatio...

Page 10: ...Power Sense Black Normal Neutral White Normal Light Fixture Emergency Power Out Red EREB Emerg Light Fixture Switch Backup Arrangement When normal power is present the emergency fixture is turned OFF...

Page 11: ...ol EREB AD model only When normal power is present and the switch is closed both 0 10 V controlled fixtures dim When normal power is present and the switch is open both 0 10 V controlled fixtures turn...

Page 12: ...quipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmfu...

Reviews: