echoflex EREB-AP Installation Manual Download Page 5

Echoflex Installation Guide

Emergency Bypass Load Controller

The remote device that triggers the Emergency circuit ON must provide a
normally closed, maintained dry contact closure for fire alarms. When the
remote device is activated, the contact closure opens and the contacts
force the EREB-AP into the emergency ON state.

Note:

When using 1 mm

2

(18 AWG) wire, the remote triggering

device, test switch, or emergency system must be installed within
305 m (1,000 ft) of the EREB.

1. Cut the blue wire loop in the middle of the wire lead. Doing this

provides two leads, which are the connection points for both the
contact input and contact output to a remote triggering device.

2. Connect the two leads to the normally closed single pole contacts on

the remote device or test switch.

3. Go to

Remote Activation Test on page 9

to confirm the connection.

Model EREB-AD

The EREB-AD is designed to attach to lighting control panels or electrical
enclosures that are fitted with a DIN rail.

Six screw terminals on the bottom of the device are used to connect
normal sense and emergency power wires. Four screw terminals on the
top of the device are used for the following connections:

The two terminals on the left have a factory-installed wire loop
(jumper). It provides a connection to a remote triggering device
(normally closed, dry contact closure, such as a fire alarm). When the
normally closed contact is triggered, the contact input opens,
activating the emergency lighting.

The two terminals on the right provide termination of 0–10 V, LED
driver loads, or fluorescent lighting control.

1. Snap the device onto an installed DIN rail in the upright position at

least 5 cm (2 in) away from any heat-generating devices. Tension clips
on the device provide an audible click when the device is installed
properly.

2. Terminate the EREB-AD to the emergency lighting for the area

controlled as shown in the

Wiring Diagram on the next page

.

a. Connect

Emergency Power In

and

Emergency Power Out

wires to

the screw terminals on the device in series with the emergency
lighting.

b. Connect the

Neutral

for the emergency circuit to the

Emergency

Neutral

screw terminal.

3. Connect the EREB-AD to the normal lighting and control device for

the area controlled.

Emergency Bypass Load Controller

Page 5 of 12

Echoflex

Summary of Contents for EREB-AP

Page 1: ...operation The EREB ensures a lights on override by using a normally closed emergency contact closure that interfaces with fire alarm and emergency systems The EREB is available in two models to provi...

Page 2: ...e c blage du courant alternatif v rifiez que les disjoncteurs pour l alimentation normale et pour l alimentation de secours sont en position d arr t et suivez les proc dures de v rouillage tiquetage p...

Page 3: ...y to the exterior of the junction box or panel either at the electrical lighting load or before the loads in the circuit See Examples of Use on page 10 Two sets of wire bundles are provided on the top...

Page 4: ...ow for wiring instructions 7 Replace the cover plate and restore power to the circuits Wiring Diagram Emergency Bypass Load Controller EREB AP Remote LED Option Button Status LED Emergency Power In Bl...

Page 5: ...ect normal sense and emergency power wires Four screw terminals on the top of the device are used for the following connections The two terminals on the left have a factory installed wire loop jumper...

Page 6: ...nnect to the terminals labeled 0 10 V FLO See Examples of Use on page 10 for more information 6 Are you are installing a remote triggering device to remotely activate the emergency circuit No Go to In...

Page 7: ...o your EREB See Initial Test on page 8 2 Remove the wire loop jumper from the Remote Loop In and Remote Loop Out terminals 3 Connect the Remote Loop In and Remote Loop Out terminals on the EREB AD to...

Page 8: ...ghting is not required 4 Confirm the automatic emergency On functionality by turning Off the circuit breaker in the normal panel The connected emergency lighting should immediately turn On again and t...

Page 9: ...ntrol circuit thereby illuminating the load and bypassing the normal control signal to the load In a properly operating system the load should illuminate upon pressing the Test button Remote Activatio...

Page 10: ...Power Sense Black Normal Neutral White Normal Light Fixture Emergency Power Out Red EREB Emerg Light Fixture Switch Backup Arrangement When normal power is present the emergency fixture is turned OFF...

Page 11: ...ol EREB AD model only When normal power is present and the switch is closed both 0 10 V controlled fixtures dim When normal power is present and the switch is open both 0 10 V controlled fixtures turn...

Page 12: ...quipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmfu...

Reviews: