background image

Echoflex Installation Guide

Tunable White Dimming Controller

Tunable White Dimming Controller

 Page 3 of 8

Echoflex

Installation 

All local codes and standard electrical practices should be observed. Ensure 
that the junction box is clean and free of obstructions and that all wiring is 
installed correctly. 

Install the Controller

Mount the controller directly to the exterior of the junction box or panel 
either at the electrical load or before the load in the circuit.

Review these instructions completely before installing the controller.

1. Locate the circuit breaker panel and terminate power to the circuit.

2. Remove the cover plate and other hardware from the junction box to 

access the wiring.

3. Mount the controller.

4. Refer to the wiring diagram to connect the controller to line power, 

neutral, and load wires. Use wire nuts on all connections and 
individually cap any bare wires, except the orange antenna wire.

5. Connect the gray and the striped violet/red wires to the driver or 

ballast’s dimming interface. Connect the striped violet/green 0-10 V 
analog color control output wire to the tunable white input on the LED 
driver.

6. Replace the electrical box cover plate.
7. Restore power to the circuit.

Note:

Follow applicable NEC and local electrical code 
requirements when installing and powering the 
controller.

Note:

The Micro USB port is for factory use only. Do not attach 
cables or accessories to this port.

Summary of Contents for ELED2

Page 1: ...external setpoint input from a gateway or outdoor CCT sensor This document covers installation of ELED2 Tunable White Dimming Controller models The Echoflex Tunable White Dimming Controller ELED2 Configuration Guide is available for download at echoflexsolutions com The package contents includes the controller and the installation guide Prepare for Installation Echoflex recommends paying special a...

Page 2: ...lectric shock This device utilizes high voltage and should only be installed by a qualified installer or electrician Follow all local codes for installation Before terminating the AC power wiring verify that the main breaker is in the off position and follow the proper lockout tag out procedures per NFPA Standard 70E AVERTISSEMENT Risque de décharge électrique Cette appareil utilise une haute tens...

Page 3: ...cuit 2 Remove the cover plate and other hardware from the junction box to access the wiring 3 Mount the controller 4 Refer to the wiring diagram to connect the controller to line power neutral and load wires Use wire nuts on all connections and individually cap any bare wires except the orange antenna wire 5 Connect the gray and the striped violet red wires to the driver or ballast s dimming inter...

Page 4: ...onic Ballast or LED Driver ELED2H 20 A 240 277 VAC Electronic Ballast or LED Driver ELED2H 16 A 347 VAC Electronic Ballast or LED Driver Dimming COM to others 0 10 V Dimming 100 mA MAX sinking current CCT 0 10 V Control 100 mA MAX sinking current Violet with Red stripe Analog Color control Violet with Green stripe Antenna orange Do not cut or cap Max Dimming Load 100 mA sinking Max Impulse Voltage...

Page 5: ...st or LED driver The orange wire is an antenna Do not cut cap or connect this wire Use only UL approved wire when making connections to the controller see table below Connection Wire Color Specification Load Red 14 AWG 600 V Neutral White 14 AWG 600 V Line Black 14 AWG 600 V Dimming 0 10 V Violet with Red 18 AWG 600 V Analog color control Violet with Green 18 AWG 600 V Dimming GND Gray 18 AWG 600 ...

Page 6: ...oller will unlink it from that controller Clear Button The Clear button resets the controller either to its pre commissioned state or to its factory default state To reset to pre commissioned state 1 Press the Clear button until the Power and Learn LEDs start blinking 2 Release the Clear button The LEDs repeat a blink code by color to indicate the type and number of devices linked to each channel ...

Page 7: ... for each channel by LED color Long blinks type Short blinks count Red Channel 1 Dimming Green Channel 2 Tunable White Description Power LED Learn LED Switch es 1 long blink followed by short blinks counting switches Off Occupancy sensor s 2 long blinks followed by short blinks counting sensors Off Photo sensor max 1 3 long blinks followed by 1 short blink counting sensor Off Central command 4 lon...

Page 8: ...ed by short blinks counting sensor Off Central command 2 long blinks followed by short blinks counting devices Off Activity Power LED Learn LED Relay Light Link mode Blink On solid Toggle Store link ID On 4 seconds On solid On 4 seconds Clear link ID Off 4 seconds On solid Off 4 seconds Factory default On solid One blink on power up On solid FCC Part 15 231 Contains FCC ID SZV STM300U This device ...