Next Generation Intelligent Lon® EIA/ANSI 709 Router
Provisional Installation Guide
22/10/2009
1
Rev1.0
Copyright Control Network Solutions Ltd 2009
Quick Installation Notes
These notes should be used in conjunction with the LonFibre router data sheet and the
latest Echelon’s Router and Repeater User’s Guide 078-0018-01A
Power Connection and Supply
Warning - Power inputs are polarity insensitive.
Typical Power input: 24VDC @150mA, power on indicator green LED.
{Operating voltage: ± 10-50 VDC or 12-30 VAC}
Lon Copper Port Installation
These should be connected in accordance with the appropriate requirements as set
down by Echelon for the specific LonTransceiver type.
Fibre Port Installation
Fibre ports must always be connected so that a left port is connected to a right port of
the next node in the ring. Segments must obey the same rules; i.e. even if only two
nodes are connected, the left port of one must connect to the right port of the next.
All connections must be made with multimode or singlemode Fibre optic cable.
Minimum use of patch panel connections is recommended, as each patch introduces
optical loss.