Next Generation Intelligent Lon® EIA/ANSI 709 Router 

Provisional Installation Guide 

22/10/2009 

Rev1.0 

 Copyright Control Network Solutions Ltd 2009   

 

 

 

Quick Installation Notes

 

 

These notes should be used in conjunction with the LonFibre router data sheet and the 

latest Echelon’s Router and Repeater User’s Guide 078-0018-01A 

 

Power Connection and Supply 

Warning - Power inputs are polarity insensitive. 

Typical Power input: 24VDC @150mA, power on indicator green LED.   

{Operating voltage: ± 10-50 VDC or 12-30 VAC}  

 

 

Lon Copper Port Installation 

These should be connected in accordance with the appropriate requirements as set 
down by Echelon for the specific LonTransceiver type. 

 

Fibre Port Installation 

Fibre ports must always be connected so that a left port is connected to a right port of 
the next node in the ring. Segments must obey the same rules; i.e. even if only two 
nodes are connected, the left port of one must connect to the right port of the next. 
All connections must be made with multimode or singlemode Fibre optic cable. 
Minimum use of patch panel connections is recommended, as each patch introduces 
optical loss. 
 
 