Eccotemp EZ-Flush i12 Use & Care Manual Download Page 34

32

Product Support: Eccotemp.com/help-desk            Shop Online: Eccotemp.com/products          Store Locater: Eccotemp.com/locater

Phone: 866-356-1992 | Email: [email protected] | Address: 315 - A Industrial RD Summerville, SC 29483

PLEASE NOTE: THIS MANUAL IS SUBJECT TO CHANGE AT ANYTIME, TO ENSURE THIS MANUAL IS UP TO DATE PLEASE VISIT OUR HELPDESK AT WWW.ECCOTEMP.COM 

FOR ALL OF OUR PRODUCT MANUALS.

PLEASE NOTE: THIS MODEL IS FOR INDOOR PERMANENT INSTALLATIONS ONLY.

Eccotemp Systems ,LLC

Limited Warranty Information

i12 LP & NG

Eccotemp hereby warrants this product to be free of material defects in materials and workmanship when

installed and operated according to Eccotemp’s installation and operating instructions. This Limited Warranty

extends to the original purchaser and subsequent owners, but only while the product remains as the site of

the original installation. This Limited Warranty terminates if moved or reinstalled at a new location. There

are no warranties, express or implied made or given other than contained in this Limited Warranty. No

agent, employee or representative of Eccotemp has any authority to bind Eccotemp to any representation

or warranty concerning the Product not contained in this Limited Warranty. Eccotemp reserves the right and

authority to change, modify or alter this warranty at any given time.

Except as expressly set forth herein, THERE ARE NO REPRESENTATIONS OR WARRANTIES, EXPRESS OR

IMPLIED, INCLUDING, WITHOUT LIMITATION, AS TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR

PURPOSE WITH RESPECT TO ANY GOODS SOLD HEREUNDER. BUYER’S EXCLUSIVE REMEDY IS LIMITED TO

REPAIR OR REPLACEMENT OF THE GOODS SOLD, AT ECCOTEMP’S DISCRETION. ECCOTEMP SHALL NOT BE

LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.

Limited Warranty Period

This Warranty is extended by Eccotemp Systems to the Owner. This warranty takes effect on the date of

installation of the Product or 30 days after the date of purchase, whichever occurs first, and is effective until

the specified anniversary of such date as follows:

Item Period of Coverage

Heat Exchanger 2 years

All other parts 2 years

Coverage’s are void if the unit is used in a hot water circulation loop, in series with a circulation system or

where an on-demand recirculation system is not incorporated.

Owner is responsible for all other costs incidental to repair such as labor, shipping, delivery and permits.

Proof of purchase required. Products repaired will be covered under this Limited Warranty for the remainder

of term of the original purchase.

Exclusions

Please refer to the Installation Manual and Use & Care Manual supplied with your new Eccotemp Systems product. 

This Limited Warranty becomes null and void if any of the following are determined to be a contributing factor by 

Eccotemp to the failure of the product:

1.     Abuse, misuse, alteration, neglect or misapplication.

2.     Improper, dangerous, destructive maintenance procedures or inadequate maintenance.

3.     Damages caused by services performed by servicers other than Eccotemp Systems.

4.     Installation in a corrosive or otherwise destructive environment.

5.     Damage as a result of freezing within the unit or surrounding piping.

6.     Scale buildup.

7.     Incorrect gas or water pressure.

8.     Acts of force Majeure.

9.     Damage as a result of use with non-portable, untreated or poorly treated well water, or water with high

         PH levels or hardness levels in excess of 12 grains per gallon (200mg/L).

10.   Incorrect sizing for the application.

11.   Products with original serial numbers that have been removed or altered and cannot be readily determined.

12.   Acts of God including, but not limited to; fire, flood, or nature disaster.

Summary of Contents for EZ-Flush i12

Page 1: ......

Page 2: ...ation of the heater in the location speci ed by the manufacturer Local codes shall govern installation of relief devices For safe operation of the water heater the relief valve must not be removed or...

Page 3: ...ithin it seek professional advice Any questions regarding the operation maintenance service or warranty of this water heater should be directed to the seller from whom it was purchased If additional i...

Page 4: ...There are many important safety messages in this manual and on your appliance Always read and obey all safety messages This is the safety alert symbol Recognize this symbol as an indication of Importa...

Page 5: ...at initial start up and at least annually thereafter Refer to the Care and Cleaning section of this manual for more information regarding flue terminal inspection WARNING Gasoline as well as other fl...

Page 6: ...is on To find water temperature being delivered turn on a hot water faucet and place a thermometer in the water stream and read the thermometer The temperature of the water at the outlet of the water...

Page 7: ...ury or fire do not connect the water heater to a fuel type not in accordance with the unit data plate propane for propane units and natural gas for natural gas units These units are not certified for...

Page 8: ...cable local codes shall govern installation For residential water heaters of a capacity greater than 52 gallons or tankless style consult the local building jurisdiction code for acceptable bracing pr...

Page 9: ...ng must be provided The unit should not be installed in the same room with a gas stove When determining the floor clearance a clearance of 6 inches must be maintained between the vent pipe and combust...

Page 10: ...lines should be insulated to conserve water and energy The water heater must be located so it is not subject to physical damage for example by moving vehicles area flooding etc The water heater shoul...

Page 11: ...oors each opening must have a minimum net free area of not less than one square inch per 2 000 Btuh of the total input rating of all the appliances in the enclosure If ducts are used the minimum dimen...

Page 12: ...5 gpm Additional water pressure is required for long pipe runs and outlet fitting s water pressure drops To maintain proper performance ensure sufficient water supply pressure The Required Water Press...

Page 13: ...led between the relief valve and the water heater Discharge from the relief valve should be piped to a suitable drain to eliminate potential water damage Piping used should be of a type approved for t...

Page 14: ...s than psi 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test p...

Page 15: ...TO DATE PLEASE VISIT OUR HELPDESK AT WWW ECCOTEMP COM FOR ALL OF OUR PRODUCT MANUALS PLEASE NOTE THIS MODEL IS FOR INDOOR PERMANENT INSTALLATIONS ONLY NOTICE The National Fuel Gas Code NFGC mandates a...

Page 16: ...oles in the water heater onto the expansion screws hang it up and screw the nuts tightly 2 Put the vent pipe through the holes in the wall and connect the elbow with the water heater and vent pipe C V...

Page 17: ...t Support isolation hanging bands should be used DO NOT use wire See diagram below DANGER Failure to install the vent adapter and properly vent the water heater to the outdoors as outlined in the Vent...

Page 18: ...n of the unit is evacuated from the appliance A 1 4 per foot upward slope is acceptable when it is not possible to vent with a downward slope however a approved Category III Stainless Steel condensate...

Page 19: ...ling the water heater Continued US Installations1 Canadian Installations2 A Clearance above grade veranda porch deck or balcony 12 in 30 cm 12 in 30 cm B Clearance to window or door that may be opened...

Page 20: ...kW 12 in 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW K Clearance to a mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3 m ho...

Page 21: ...COM FOR ALL OF OUR PRODUCT MANUALS PLEASE NOTE THIS MODEL IS FOR INDOOR PERMANENT INSTALLATIONS ONLY Installing the water heater Continued WARNING Use UL approved Category III vent material only No ot...

Page 22: ...found inside of the cover panel A green screw is provided in the junction box for grounding connection Connect the live wire to black leg wire and the neutral wire to the white neutral wire Electrica...

Page 23: ...structions included with the kit must be carefully followed Insulation Blankets Hot and Cold Pipe Insulation Installation For increased energy efficiency use pipe insulation Please install the insulat...

Page 24: ...oom to service heater Combustible materials such as clothing cleaning materials rags etc clear of the heater and vent piping Water heater is properly attached to the wall B Water Supply Water supply h...

Page 25: ...ight any appliance DO NOT touch any electric switch DO NOT use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you canno...

Page 26: ...ner still fails to ignite turn off the faucet and wait for 10 20 seconds and repeat the above procedures For first use and or if the water heater has not been used for a considerable period of time th...

Page 27: ...hipped from the factory This is the recommended starting point Water temperatures above 120 F can cause severe burns or death from scalding The thermostat is adjusted to its lowest temperature positio...

Page 28: ...uld be cleaned monthly Refer to the Housekeeping section for further information DO NOT operate the water heater if you feel something is wrong with the unit DO NOT allow children to operate or otherw...

Page 29: ...rate the unit if vent system shows signs of leaking exhaust Check to make sure that the Air Intake and the vent terminal have not been blocked or contain debris Vacation and Extended Shut Down If the...

Page 30: ...F position and disconnect breaker at least 10 seconds after step 1 5 Open drain valve 6 Open all hot water faucets Before proceeding to the next step make sure that COLD water is coming out of all hot...

Page 31: ...hutoff valve and open fully Hot water faucet is not fully opened Open hot water faucet completely The main burner goes off when incoming water volume is inadequate Water piping is frozen Allow piping...

Page 32: ...olenoid valve Open circuit of the valve short circuit of the valve none of the above Connect the valve replace the valve replace the computer board If the error code remains shown Close the hot water...

Page 33: ...ame sensor Flame sensor board Solenoid valve Gas inlet pipe Back cover Power cord Gas flute Water inlet pipe Computer board Wind switch Clip Hot water temp sensor Replacement Parts For models using na...

Page 34: ...UENTIAL DAMAGES Limited Warranty Period This Warranty is extended by Eccotemp Systems to the Owner This warranty takes effect on the date of installation of the Product or 30 days after the date of pu...

Page 35: ...cing the unit shipping delivery and handling of the replacement part cost for permits or materials necessary for the repair or incidental costs resulting from damage external to the unit resulting fro...

Page 36: ......

Reviews: