4
Technische Daten
Gas-Gebläsebrenner
E 10.12000/14000 G-EU2
LowNox
mit
Delta
Brennkopf
Technical Data
Gas/light oil Forced Draught Burner
E10.12000/14000 L-EUF
Stand: 20.10.2005
Market Launch
E10.14000 L-EUF Available not yet defined
Burner weight
Approx . 650 kg plus 100 kg for transport rack
CE-Conformity
No CE-Confirmity, Equipment for heat generator, Single audit necessary (see
manufacturer declaration), Homologation according European directives planned for
2006
Acoustic Emission - Sound Pressure
< 97 dBA (average value on enveloping surface at 1 m distance)
Max. temperature of operating material
max. 60°C (including impact from heat radiation)
Flame length max. at 3% O
2
5,9 m
6,4 m
Flame Diameter
(depends on NOx requirements)
1,3 - 1,6 m
1,4 - 1,75 m
Protection Class
IP40, IP54 as option
NOx-Emissionen
Emission Class 3 according EN267
Oil operation: 120-200 mg/kWh (0% O2 acc. EN267)
Detailed values on request
Oil connection
High pressure pump 30 bar mounted on burner
approx. 2700 l/h; 4,0 kW
approx. 4000 l/h; 5,5 kW
Fan motor
400/690 V, 50/60 Hz, 2950/3550 U/min, IP55
37 kW
45 kW
Operation Type
Continuously modulating
Electronic Air-Fuel-Compound-Control
Automatic Firing Device
Etamatik OEM or BCS 300 on burner
Alternative electronic burner controls in separate cabinet
Fuels
Fuel Oil EL
Max. control ratio
(FQ=frequency converter for motor)
1:3,5 bei Fuel oil EL
1:3,5 for Fuel oil EL
Deviating values on request
Low NOx with Free-Flame Combustion Technology
Electronic Fuel-Air-Control
E10.12000.37 L-EUF
E10.14000.45 L-EUF
Combustion Power Output
Fuel Oil EL: 1500 - 12.000 kW
Fuel Oil EL: 1750 - 14.000 kW
Boiler Furnace Pressure
According line of operation field and 10 mbars less.
Deviating values on request.
Operation Fields E10 L-EUF according EN 267
0
5
10
15
20
25
30
35
40
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Combustion Power Output [MW]
Boi
le
r Fur
nace Pr
essur
e [
m
bar
]
E10.14000.45 L-EUF
E10.14000.45 L-EUF with FQ
E10.12000.37 L-EUF