Chengdu Ebyte Electronic Technology Co.,Ltd.
E90-DTU(433L30E)-V8 User Manual
Copyright ©2012–2022,Chengdu Ebyte Electronic Technology Co.,Ltd.
34
Configurable gateway configuration (the picture on the left is the host computer, and the picture on the right is the
webpage):
5.8.6. Automatic upload
In the client mode (TCP client, UDP client, etc.), the gateway will automatically poll the instructions in the stored
instruction table and upload it to the server. The feedback format (Modbus RTU format or Modbus TCP format)
and the instruction polling interval can be selected according to requirements. (0-65535ms).
For instruction pre-storage, refer to "Configurable Gateway - Instruction Storage Instructions", and automatically
upload the upper computer/web page configuration:
TCP client demonstration (Modbus RTU format on the left, Modbus TCP format on the right):