Ebsray RC SERIES Installation, Operation & Maintenance Instructions Manual Download Page 7

 

11.  Screw  in  the  Bypass  Valve  Adjusting  Screw,  not 

exceeding  two  turns  per  minute  until  the  desired 
differential pressure is reached.  

12.  While  retaining  the  Adjustment  Screw,  lock  the 

Adjusting  Screw  Lock  Nut  against  Bypass  Valve 
Cover immediately after adjustment is made. 

13.  After the setting of the Bypass Valve is completed, 

wire  and  seal  Adjusting  Screw,  utilising  holes 
provided  for  passing  wire  through  head  of 
Adjusting Screw and lug on Bypass Valve Cover. 

Bypass 

Valves 

characteristically 

exhibit  two  distinct  pressures  during 
their operation: 

a)

 

The 

‘setting’  or  ‘cracking’  pressure  which 

occurs when the Bypass Valve first opens i.e. 
initial  bypassing  begins  against  the  preset 
spring load, and;

 

b)

 

‘Maximum’  pressure,  which  occurs  when  the 

full  flow  of  the  bypassed  product  passes 
through the Bypass Valve.

 

It  is  important  to  ensure  both  these  above 
characteristics are understood fully in order to 
correctly apply the Bypass Valve.

 

If any aspect of the 
Pumpset or pumping 
system does not 

function properly, immediately turn the pump 'off' 
and rectify the problem before re-starting. 

14  Record  discharge  pressure  in  the  commissioning 

section of the Pump Run Log. 

15.  Check that motor current is below FLA rating. 
 

Record  the  motor  current  readings  in  the 
commissioning section of the Pump Run Log

.

 

NOTE: 

During  this  procedure,  or  at  any  time, 

motor  current  must  not  exceed  FLA  rating  of 
motor.

 

16.  Stop pump, restart and check for consistent results, 

rectify if required. 

17.  Record discharge pressure and current readings in 

the commissioning section of the Pump Run Log.

 

18.  The Pumpset is now ready for normal operation. 

19.  The start-up procedure is now complete. 

20.  Inspect Pumpset/pumping system frequently during 

the  first  few  hours  of  operation  then  periodically 
thereafter (see Section 4.5 for frequency). 

 

Record  the  observations  from  these  inspections  in 

the Pump Run Log

 
 
 
 
 
 
 
 
 
 
 
 
 

4.5  PERIODIC INSPECTION 

Periodic  Inspection  of  the  Pump,  Pump  System  and 
Ancillary  Equipment  is  required  to  maintain  safety, 
conformity,  operational  functionality  and  reliability. 
Ebsray  recommends  a  maximum  interval  of  three 
months  or  500  hours  operation  between  routine 
periodic  maintenance  inspections  (More  frequent 
inspections  may  be  necessary  dependent  upon 
usage, site conditions, operation etc). 

If  any  abnormal  condition  is  discovered,  cease 
operation  of  pump  immediately  and  take  action  to 
rectify  the  problem.  Record  observations  from  these 
inspections in Pump Run Log. 

For  safe  operation,  the  following  items  should  be 
included in the routine periodic inspection: 
a. 

Inspect  the  Pump  for  LPG  leaks,  vibration, 

abnormal 

noises, 

signs 

of 

overheating, 

discolouration, etc. 

b. 

 Inspect  Coupling  Assembly  for  signs  of  wear, 

overheating, discolouration, etc. 

c. 

Check Pump differential pressure 

d. 

Check Motor Current. 

e. 

Inspect motor for vibration, abnormal noises, signs 

of overheating, discolouration, etc. 

WARNING
ER 

NOTE:

 

Summary of Contents for RC SERIES

Page 1: ...Publication 1987 16EN EBSRAY PUMPS INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS RC SERIES MODELS RC20 RC25 RC40...

Page 2: ...e 5 3 1 6 Bypass Valve 6 SECTION 4 OPERATION 6 4 1 DESCRIPTION 6 4 2 LUBRICATION 6 4 3 PRE STARTUP CHECKLIST 6 4 4 COMMISSIONING START UP PROCEDURE AND BYPASS ADJUSTMENT 6 4 5 PERIODIC INSPECTION 7 SE...

Page 3: ...ions within this Publication and any other relevant Ebsray documents are STRICTLY adhered to b Any variation including use of equipment deemed Equivalent or addition to the Ebsray Specifications as re...

Page 4: ...e and current Should any change be contemplated please confer with Ebsray in order to verify the suitability of such a change 1 2 TRANSPORTATION PACKING STORAGE Standard domestic packing is suitable f...

Page 5: ...installed When mounted direct on a concrete foundation ensure that it has a solid footing and is levelled on the pump mounting surfaces b Ensure floor area and headroom allotted is sufficient for insp...

Page 6: ...by Ebsray or customer supplied 4 2 LUBRICATION The Ball Bearings for the RC Series pumps are grease lubricated and sealed for life design No in service lubrication is required on Ebsray s RC Series Pu...

Page 7: ...motor current must not exceed FLA rating of motor 16 Stop pump restart and check for consistent results rectify if required 17 Record discharge pressure and current readings in the commissioning secti...

Page 8: ...2 Remove Cover Impeller and Impeller Key The Coupling Guard retaining screws may be screwed into the Impeller to aid removal 3 Unscrew four grubscrews from Cartridge Ref Fig 2 4 Insert grubscrews int...

Page 9: ...e all O Rings be replaced at every overhaul or when any disassembly is conducted 5 6 SPARE PARTS 1 When ordering spare parts to ensure a minimum of delay and correct replacement to original specificat...

Page 10: ...one with a compatible good quality detergent free light oil and fit Quill Assembly to Body 9 Lock in place with 4 grubscrews apply Loctite 243 or equivalent to grubscrews Fig 16 Refer Fig 16 10 Fit Ke...

Page 11: ...ge Mechanical Seal 1 incl 36D Half Coupling Motor 1 57A Grubscrew 4 incl 36E Coupling Element 1 57B O Ring Cartridge Primary 1 incl 36P Half Coupling Pump 1 57C O Ring Cartridge Secondary 1 58 Circlip...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Reviews: