8
Systemdescription
5.3
AS interface
5.3.1 AS interface connection
AS interface (Actuator Sensor Interface) is a field bus system which
is used primarily for networking binary sensors and actuators (slaves)
with a higher-level control (master).
Bus line
Unshielded two-wire line (AS interface line as AS interface cable
harness) along which both information (data) and energy (power supply
for the actuators and sensors) are transmitted.
Network topology
Freely selectable within wide limits, i.e. star, tree and line networks are
possible. Further details are described in the AS interface specification
(A/B slave model conforms to the version 3.0 specification).
5.3.2 Technical data for AS interface PCBs
Profile version S-7.3.4
Profile version S-7.A.5
Supply
via AS interface
via AS interface
Outputs
16 bit set-point value
16 bit set-point value
Inputs
-
16 bit status feedback
Certification
Certificate no. 87301
after version 3.0
Certificate no. 95401
after version 3.0
Tab. 1: Technical data
5.3.3 Programming data for AS Interface PCBs
Profile version S-7.3.4
Profile version
S-7.A.5
I/O configuration 7 hex
7 hex
ID code
3 hex (analog profile)
A hex
Extended
ID code 1
F hex (default value, can
be changed by the user)
7 hex
Extended
ID code 2
4 hex
5 hex
Profile
S-7.3.4
S-7.A.5
Tab. 2: Programming data
Bit configuration
1. Output set-point value
(value range 0 ... 10,000 corresponds to 0 ... 100 %)
2. Input status feedback
14)
(value range 0 ... 10,000 corresponds to 0 ... 100 %)
Byte 2
0
0
D13
D12
D11
D10
D9
D8
Byte 1
D7
D6
D5
D4
D3
D2
D1
D0
Parameter bit
P3
P2
P1
P0
Output
Not used
Not used
Not used
Not used
Tab. 3: Bit configuration
english
Type EP 501 B
Summary of Contents for EP 501 B
Page 78: ...www ebro armaturen com...