background image

Operating instructions

W4D400-DP12-41

Translation of the original operating instructions

3.2 Nominal data

Motor

M4D074-EI

Phase

3~

3~

Nominal voltage / VAC

380

480

Wiring

Y

Y

Frequency / Hz

50

60

Method of obtaining
data

fa

fa

Valid for approval/
standard

-

-

Speed (rpm) / min

-1

1430

1700

Power consumption / W

145

250

Current draw / A

0.48

0.52

Max. back pressure / Pa

95

130

Min. ambient
temperature / °C

-25

-25

Max. ambient
temperature / °C

60

55

Starting current / A

1.7

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

9.375 kg

Size

400 mm

Motor size

74

Rotor surface

Painted black

Blade material

Sheet steel, painted black

Fan housing material

Sheet steel, galvanized and coated with
black plastic (RAL 9005)

Guard grille material

Steel, coated with black plastic (RAL
9005)

Number of blades

5

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent
as per EN 60034-5

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H1+

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1, motor does not have
factory-installed overheating protection

Comment on CE

Commissioning not permitted in the
European Economic Area

Approval

CSA C22.2 No. 100; UL 1004-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

Strength class of
screws

8.8

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

Item no. 13681-5-9970 · ENU · Change 219792 · Approved 2021-01-26 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W4D400-DP12-41

Page 1: ...d by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installatio...

Page 2: ...vice Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to...

Page 3: ...he following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This als...

Page 4: ...ll dimensions in mm 1 Direction of air flow V 2 Cable PFA AWG18 1x crimped splice cable PFA AWG20 3x crimped splices Item no 13681 5 9970 ENU Change 219792 Approved 2021 01 26 Page 4 11 ebm papst Mulf...

Page 5: ...0335 1 motor does not have factory installed overheating protection Comment on CE Commissioning not permitted in the European Economic Area Approval CSA C22 2 No 100 UL 1004 1 With regard to cyclic sp...

Page 6: ...be switched off with an all pole disconnection switch When working on the fan secure the system machine in which the fan is installed so as to prevent it from being switched back on NOTE Water ingress...

Page 7: ...nsulation system and against harmful bearing currents Heating up of the motor when using a variable frequency drive must be checked by the customer following installation in the end device 4 3 Connect...

Page 8: ...se motor Y Star connection 1 Counterclockwise operation L1 V1 blue L2 U1 black L3 W1 brown 2 Clockwise operation L1 U1 black L2 V1 blue L3 W1 brown PE green yellow Item no 13681 5 9970 ENU Change 2197...

Page 9: ...ure to disconnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or replacement WA...

Page 10: ...ation of cables for damage Visual inspection At least every 6 months Replace cables Condensation drainage holes for clogging where necessary Visual inspection At least every 6 months Open holes Welds...

Page 11: ...The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolytic capacitors Dispose of electronic components employing the...

Reviews: