Operating instructions
W2D170-AA04-52
Translation of the original operating instructions
3.2 Nominal data
Motor
M2D068-BF
Phase
3~
3~
3~
3~
Nominal voltage / VAC
230
230
400
400
Wiring
Δ
Δ
Y
Y
Frequency / Hz
50
60
50
60
Method of obtaining
data
fa
fa
fa
fa
Valid for approval/
standard
CE
CE
CE
CE
Speed (rpm) / min
-1
2750
3100
2750
3100
Power consumption / W
45
43
45
43
Current draw / A
0.23
0.16
0.13
0.09
Min. ambient
temperature / °C
-25
-25
-25
-25
Max. ambient
temperature / °C
50
70
50
70
Starting current / A
0.4
0.38
0.23
0.22
ml = Max. load · me = Max. efficiency · fa = Free air
cs = Customer specification · ce = Customer equipment
Subject to change
3.3 Technical description
Weight
1.8 kg
Fan size
170 mm
Rotor surface
Painted black
Blade material
Die-cast aluminum
Fan housing material
Die-cast aluminum
Guard grille material
Steel, coated with black plastic (RAL
9005)
Number of blades
6
Airflow direction
"A"
Direction of rotation
Clockwise, viewed toward rotor
Degree of protection
IP44; installation- and position-dependent
Insulation class
"B"
Moisture (F) /
Environmental (H)
protection class
H0 - dry environment
Installation position
Any
Condensation
drainage holes
None
Mode
S1
Motor bearing
Ball bearing
Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)
< 0.75 mA
Motor protection
Thermal overload protector (TOP) with
basic insulation
with cable
Lateral
Protection class
I (with customer connection of protective
earth)
Conformity with
standards
EN 60335-1; CE
Approval
UL 1004-1; CSA C22.2 No. 100
With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.
3.4 Mounting data
For screw clearance, see Chapter 3.1 Product drawing
;
Secure the screws against unintentional loosening (e.g. use self-
locking screws).
Strength class of
screws
8.8
Any further mounting data required can be taken from the product drawing.
3.5 Transport and storage conditions
;
Use the device in accordance with its degree of protection.
Max. permitted
ambient temp. for
motor (transport/
storage)
+ 80 °C
Min. permitted
ambient temp. for
motor (transport/
storage)
- 40 °C
4. CONNECTION AND STARTUP
4.1 Mechanical connection
CAUTION
Cutting and crushing hazard when removing device
from packaging
Blades can bend
→ Carefully remove the device from its packaging, by the fan
housing. Strictly avoid shocks.
→ Wear safety shoes and cut-resistant safety gloves.
NOTE
Damage to the device from vibration
Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration
from sections of the installation. #It is advisable to use spring
or rubber isolators for decoupling (not included in scope of
delivery). The fan is to be operated sufficiently far away from
the resonant frequency of the vibration isolators. #If the fan is
connected to air ducts, the connection should be isolated
from vibration, e.g. using compensators or similar elements.
→ Ensure stress-free attachment of the fan to the sub-structure.
;
Check the device for transport damage. Damaged devices are not to
be installed.
;
Install the undamaged device in accordance with your application.
CAUTION
Possible damage to the device
If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of
installation until all fastening screws have been tightened.
Item no. 12939-5-9970 · ENU · Change 84370 · Approved 2016-06-16 · Page 5 / 10