background image

Operating instructions

W1G208-BA73-12

GOOGLE USA

Translation of the original operating instructions

2. PROPER USE

The device is exclusively designed as a built-in device for moving air
according to its technical data.
Any other or secondary use is deemed improper and constitutes a
misuse of the device.
Installations on the customer's side must meet the mechanical, thermal
and service life-related stresses that can occur.

Proper use also includes:

Moving air with a density of 1.2 kg/m³.

Using the device in accordance with the permitted ambient
temperature, see chapter 3.5 Transport and storage conditions and
chapter 3.2 Nominal data.

Operating the device with all protective features in place.

Minding the operating instructions.

Improper use

Using the device in the following ways is particularly prohibited and
may cause hazards:

Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.

Moving air that contains abrasive particles.

Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.

Moving air that contains dust pollution, e.g. suctioning off saw dust.

Operating the device close to flammable materials or components.

Operating the device in an explosive atmosphere.

Using the device as a safety component or for taking on safety-
related functions.

Operation with completely or partially disassembled or modified
protective features.

In addition, all application options that are not listed under proper use.

Item no. 51090-5-9970 · ENG · Revision 83494 · Release 2014-09-25 · Page 3 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for W1G208-BA73-12

Page 1: ...ical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules An...

Page 2: ...it until all parts have come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear...

Page 3: ...in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving h...

Page 4: ...of air flow V 2 Connector housing Molex 39 01 2040 connection line AWG20 with 4x connector socket Molex 39 00 0059 2 1 red 2 2 Control input yellow 2 3 blue 2 4 S white Item no 51090 5 9970 ENG Revisi...

Page 5: ...lectrical leads With plug Motor protection Reverse polarity and locked rotor protection Cable exit Lateral Product conforming to standard EN 60950 1 Approval UL 1004 1 CSA C22 2 Nr 77 For cyclic speed...

Page 6: ...y environment Operate the device with a safely isolated power pack 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that...

Page 7: ...supply 48 VDC residual ripple 3 5 1 2 0 10 VDC yellow Control input Re 100 K 1 3 Tach white Speed monitoring output 3 pulses per rotation Isink max 10 mA 1 4 GND blue Reference mass Item no 51090 5 9...

Page 8: ...he supply voltage 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and conne...

Page 9: ...ses or solvents Do not use any pointed or sharp edged objects to clean 5 2 Safety test What has to be tested How to test Frequency Which measure Check the protective casing against accidental contact...