Operating instructions
S3G450-LC28-59
Translation of the original operating instructions
;
Route the wire(s) (not included in scope of delivery) into the terminal
box.
;
First connect the "PE" (protective earth).
;
Connect the wires to the corresponding terminals.
Use a screwdriver to do so.
When connecting, ensure that no wire ends fan out.
;
Seal the terminal box.
4.3.3 Cable routing
Water must be prevented from reaching the cable gland along the cable.
NOTE
Damage caused by moisture penetration.
Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable
glands, the cable should be routed in a U-shaped loop
wherever possible.
→ If this is not possible, a drip edge can be produced by
fitting a cable tie directly in front of the cable gland for example.
Fans installed lying flat
Make sure the cable is routed in a U-shaped loop.
Fig. 2: Fan installed lying flat, cable routed in a U-shaped loop.
Fans installed upright
When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.
Fig. 3: Cable routing for fans installed upright.
4.4 Factory settings
Factory settings made for the device by ebm-papst.
Mode
PWM control
Group address
01
Fan/device address
01
Max. PWM / %
100
Min. PWM / %
0
Save set value to
EEPROM
No
Set value requirement
Analog
Direction of action
Positive (heating)
Item no. 51268-5-9970 · ENU · Change 222738 · Approved 2021-02-01 · Page 8 / 13