Operating instructions

R3G500-AG10-13

Translation of the original operating instructions

4.6 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

;

Screw the terminal box cover closed again. Terminal box tightening
torque, see chapter 3.1 Product drawing.

;

Route the connecting cables in the terminal box so that the terminal
box cover closes without resistance.

;

Use all plug screws (the entire number). In doing so, insert the
screws manually to avoid damage to the thread.

;

Make sure that the terminal box is correctly closed and sealed and
that all screws and screwed cable glands are properly tightened.

4.7 Switch on device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the fan.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

;

Start the device by changing the input signal.

4.8 Switching off the device

Switching off the device during operation:

;

Switch off the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

Switching off the device for maintenance work:

;

Switch off the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

;

Disconnect the device from the supply voltage.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. INTEGRATED PROTECTIVE FUNCTIONS

The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.
The status relay drops out and the fault is reported via BUS.

Malfunctions

Description / Function of
safety feature

Rotor position detection error

An automatic restart occurs.

Locked rotor

;

After the blockage is

removed, the motor restarts
automatically.

Line under-voltage (mains input
voltage outside of permitted
nominal voltage)

;

If the mains supply voltage

returns to permitted values, the
motor restarts automatically.

Phase failure

A phase of the supply voltage
fails for at least 5 s.

;

If all phases are correctly

supplied again, the motor
automatically restarts after 10 -
40 s.

Item no. 50489-5-9970 · Revision 82539 · Release 2014-05-08 · Page 10 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G500-AG10-13

Page 1: ...to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re...

Page 2: ...g on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing...

Page 3: ...imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Pai...

Page 4: ...0 mm tightening torque 4 0 6 Nm 2 Accessory part Inlet nozzle 63072 2 4013 not included in the standard scope of delivery 3 Depth of screw max 25 mm 4 Tightening torque 3 5 0 5 Nm Item no 50489 5 9970...

Page 5: ...or protection Protection class I if protective earth is connected by customer Product conforming to standard EN 61800 5 1 CE Approval CSA C22 2 Nr 77 EAC UL 2111 For cyclic speed loads note that the r...

Page 6: ...ires Water enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switch...

Page 7: ...t drawing Fig 1 Recommended stripping lengths in mm inside the terminal box Legend CL control lines 4 3 2 Connecting cables with terminals WARNING Terminals and connections have voltage even with a un...

Page 8: ...tion mode PWM controlling Group adress 1 Fan device adress 1 Max PWM 100 Min PWM 0 Save set value to EEPROM Yes Set value control Analog Control function Positive heating Item no 50489 5 9970 Revision...

Page 9: ...quate to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input...

Page 10: ...remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch of...

Page 11: ...ge Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts...

Page 12: ...ainst accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visu...