Operating instructions

R3G355-AM08-32

Translation of the original operating instructions

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing fan from
packaging

→ Carefully remove the device from its packaging, by the fan

impeller. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

4.2 Electrical connection

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Operate the device with a safely isolated power supply.

4.2.1 Requirements

;

Check whether the data on the nameplate match the connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

4.3 Connecting the cables

The device has external leads.

Connect the cables according to your application. When doing so,
observe Chapter 4.4 Connection diagram.

Item no. 51826-5-9970 · ENU · Change 89187 · Approved 2016-04-14 · Page 6 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G355-AM08-32

Page 1: ...ly qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic...

Page 2: ...the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and...

Page 3: ...with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an...

Page 4: ...able PVC AWG16 4x crimped ferrules 2 Accessory part inlet ring 35560 2 4013 not included in scope of delivery 3 Clearance for screw 12 14 mm Item no 51826 5 9970 ENU Change 89187 Approved 2016 04 14 P...

Page 5: ...etermined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 4 9 kg Fan size 355 mm Rotor surface Painted black Electronics housing material Die ca...

Page 6: ...the cable can damage the device Make sure the end of the cable is connected in a dry environment Operate the device with a safely isolated power supply 4 2 1 Requirements Check whether the data on the...

Page 7: ...pply 48 VDC maximum ripple 3 5 1 2 PWM yellow PWM level 2 8 V 20 V cable break detection 1 3 Tach white Tach output open col 3 pulses per revolution Isink max 10 mA 1 4 GND blue Reference ground Item...

Page 8: ...e terminals and connections even with device switched off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION If control voltage or a stored...

Page 9: ...cific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 5 3 2 Disassembly...

Reviews: