Operating instructions
R3G310-FR04-I1
Translation of the original operating instructions
3.2 Nominal data
Motor
M3G084-DF
Phase
1~
Nominal voltage / VAC
230
Nominal voltage
range / VAC
200 .. 277
Frequency / Hz
50/60
Method of obtaining
data
ml
Speed (rpm) / min
-1
2750
Power consumption / W
750
Current draw / A
3.3
Min. ambient
temperature / °C
-40
Max. ambient
temperature / °C
50
ml = Max. load · me = Max. efficiency · fa = Free air
cs = Customer specification · ce = Customer equipment
Subject to change
3.3 Data according to Commission Regulation (EU) 327/
2011
Actual
Req. 2015
01 Overall efficiency η
es
/ %
68.4
50.1
02 Measurement category
A
03 Efficiency category
Static
04 Efficiency grade N
80.3
62
05 Variable speed drive
Yes
06 Year of manufacture
The year of manufacture is specified on the
product's rating label.
07 Manufacturer
ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen
08 Type
R3G310-FR04-I1
09 Power consumption P
ed
/ kW
0.73
09 Air flow q
v
/ m³/h
2805
09 Pressure increase total p
sf
/
Pa
592
10 Speed (rpm) n / min
-1
2750
11 Specific ratio
*
1.01
12 Recycling/disposal
Information on recycling and disposal is
provided in the operating instructions.
13 Maintenance
Information on installation, operation and
maintenance is provided in the operating
instructions.
14 Additional components
Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.
*
Specific ratio = 1 + p
fs
/ 100 000 Pa
Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller
combination in a standardized measurement setup.
3.4 Technical description
Size
310 mm
Motor size
84
Rotor surface
Painted black
Electronics housing
material
Die-cast aluminum
Impeller material
PP plastic
Number of blades
6
Direction of rotation
Clockwise, viewed toward rotor
Degree of protection
IP55
Insulation class
"F"
Moisture (F) /
Environmental (H)
protection class
H1
Ambient temperature
note
Occasional start-up at temperatures
between -40°C and -25°C is permitted.
For continuous operation at ambient
temperatures below -25°C (such as
refrigeration applications), use must be
made of a fan design with special low-
temperature bearings.
Installation position
Shaft horizontal or rotor on bottom; rotor
on top on request
Condensation
drainage holes
On rotor side
Mode
S1
Motor bearing
Ball bearing; (sealed)
Technical features
- Output 10 VDC, max. 10 mA
- Operation and alarm display
- Alarm relay
- Integrated PID controller
- Power limiter
- Motor current limitation
- PFC, active
- RS-485 MODBUS-RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection
Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)
<= 3.5 mA
Motor protection
Thermal overload protector (TOP)
internally connected
with cable
Variable
Protection class
I (with customer connection of protective
earth)
Conformity with
standards
EN 60335-1; EN 61800-5-1; CE
Approval
CSA C22.2 No. 77 + CAN/CSA-
E60730-1; EAC; UL 1004-7 + 60730-1
Item no. 57038-5-9970 · ENU · Change 213992 · Approved 2020-07-16 · Page 6 / 12